⚡ANMASystem BuildingAutomation, Network, Monitoring & Analytics
★PREMIUM

Knowledge Base › Batteries

Pylontech Force-H2-V2

Verified distributor GLOBAL verified Sept. 20, 2026

Unresolved safety-relevant conflict
Two sources give different figures for a value on this product and nobody has resolved it. The specifications below are shown as recorded, but this product must not be treated as verified for engineering purposes until the conflict is closed.

Identity

category batteries
ean —
firmware {'documented_version': 'SMA requires battery firmware >= 1.2.0.R for Force-H2-V2', 'constraints': 'Inverter-side minimums differ per inverter - see documented_relationships.'}
generation V2 hardware revision
manufacturer Pylontech
market_version EU approval lists (KOSTAL, SMA) print this revision explicitly
model Force-H2-V2
mpn Battery module FH9637M; control module FC0500M-40S-V2
product_family Force H2
product_status —
region GLOBAL
release_year —
series Force (high voltage)
sku —
variant V2

Electrical

bms Control Module FC0500M-40S-V2 (internal power supply, LED status display, start / black-start buttons, power switch, Wi-Fi)
cell_chemistry Li-iron (LFP)
cell_configuration 30 cells in series per module, 3.2 V / 37 Ah per cell
communication CANBUS / Modbus RTU; CAN default 500 kbps, Modbus RTU default 9600 baud; CAN, RS485, RS232 and Link0/Link1 RJ45 ports
depth_of_discharge_pct 95
expandable_to_kwh 14.20 kWh per group per the operation manual (4 x FH9637M); up to 6 groups per system, i.e. up to 24 modules
max_charge_current_a 18.5 A normal; 42 A max @15 s
max_charge_power_w —
max_discharge_current_a 18.5 A normal; 42 A max @15 s
max_discharge_power_w —
module_capacity_ah 37
module_nominal_energy_kwh 3.552
module_nominal_voltage_v 96
modules_per_stack 2 to 4 FH9637M battery modules per group (operation manual V1.0). CONFLICTS with KOSTAL's 07/2026 sheet, which prints 2-5 modules - see data_conflicts.
nominal_energy_kwh 7.10 (2 modules) / 10.65 (3 modules) / 14.20 (4 modules) - as printed in the manual's system-configuration table
nominal_voltage_v 192 Vdc (2 modules) / 288 Vdc (3 modules) / 384 Vdc (4 modules)
parallel_units_max 6
peak_discharge 42 A for 15 seconds
round_trip_efficiency_pct 96
usable_energy_kwh 6.75 kWh
voltage_range_v Per stack as printed: 2 modules 174-216 Vdc, 3 modules 261-324 Vdc, 4 modules 348-432 Vdc (lower discharge voltage to upper charge voltage)

Physical / mechanical

ac_terminal not applicable - DC battery
cooling —
dc_connector Supplied cables: DC+ 3 m red 8AWG, DC- 3 m black 8AWG, ground 1 m yellow-green 10AWG
depth_mm 296
dimensions_mm Stack: 450*296*822 (2 modules) / 450*296*1118 (3 modules) / 450*296*1414 (4 modules) (W*D*H, as printed)
display LED status display on the control module
enclosure_material —
height_mm 822 / 1118 / 1414 depending on stack size
module_dimensions_mm Battery module FH9637M 450*296*296 mm, 35 kg; control module FC0500M-40S-V2 450x296x190 mm; base 450x296x40 mm
mounting Floor-standing stack on a base (450x296x40 mm) fixed with 4 pcs M8x80 foundation bolts; bracket fasteners 14 x M4 screws
noise_db —
weight_kg 82 (7.10 kWh) / 117 (10.65 kWh) / 152 (14.20 kWh)
width_mm 450

Installation

cable_requirements DC+ 3 m 8AWG, DC- 3 m 8AWG, ground 1 m 10AWG, communication 3 m RJ45 x2 and 1.5 m internal RJ45; RJ45 connectors with water-proof M19 covers
commissioning Register the product at www.pylontech.com.cn/service/support for full warranty. If stored for more than 3 months, charge every six months and keep SOC no less than 90%; recommended full charge every 3 months during continuous operation for balancing.
installation_angle —
mounting_clearances More than 2 metres from heat sources; more than 0.3 metres from the battery module/rack; suggested base height >=300 mm above ground
torque UNKNOWN - no torque table was printed in the manual read; grounding resistance must be <=100 mOhm

Environment

ingress_protection IP55
max_altitude_m <2000
operating_temperature_c 0~50℃ (charge and discharge); optimum 18℃~28℃
pollution_degree —
protective_class —
relative_humidity_pct 5~95%
storage_temperature_c -20~60℃

Interfaces & connectors

app —
communication ['CAN', 'RS485', 'RS232', 'Link0/Link1 (master/slave daisy-chain)', 'Wi-Fi']
dry_contact —
meter_interface —
monitoring_portal —
protocols ['CANBUS', 'Modbus RTU']

Protection

anti_islanding not applicable - DC battery
arc_fault —
dc_switch Power switch on the control module
functions Over/under temperature, over/under voltage, over current, short-circuit (<4000 A rating), automatic cell balancing, communication-loss detection, relay-adhesion monitoring, black start (10 minutes)
insulation_monitoring —
overvoltage_category —
rcmu —
reverse_polarity —
surge_protection_ac —
surge_protection_dc —

Certifications

standards ['VDE-AR-E 2510-50', 'IEC62619', 'IEC63056', 'IEC62040-1', '2014/53/EU (RED)', 'UN38.3 (transfer certificate)', 'TUV SUD']

Warranty & service

conditions Product registration at www.pylontech.com.cn/service/support required for full warranty.
cycle_life 5,000 cycles (module level, as printed)
energy_throughput_mwh —
extension_options —
operation_life 15+ years
standard_years UNKNOWN - the operation manual requires product registration for 'full warranty' but prints no term

Documents

compatibility-list Compatibility List of Pylontech High Voltage ESS and Inverters Ver.2.40 rev Ver.2.40
compatibility-list KOSTAL PLENTICORE plus (G2) technical data sheet with all batteries, DOC03306755 rev DOC03306755
compatibility-list SMA Technical Information: SUNNY BOY STORAGE - Approved batteries, SBS-Batteries-TI-en-28 Version 2.8 rev Version 2.8
user-manual Lithium Phosphate Energy Storage System Force-H2-V2 Operation Manual (doc code 5PMPA08_00134, Force_H2_V2 V1.0) rev V1.0

Recorded conflicts

electrical.modules_per_stack Review required
2 to 4 modules per group (7.10 / 10.65 / 14.20 kWh) — Pylontech Force-H2-V2 Operation Manual V1.0 (2022-10-18)
2 to 5 modules, 174-540 V, 7.1-17.8 kWh — KOSTAL PLENTICORE plus (G2) tech sheet with all batteries DOC03306755, 07/2026
2 to 4 modules, 7.10-14.20 kWh — SMA SBS-Batteries-TI-en-28 Version 2.8
identity.mpn (control module part number) Review required
FC0500M-40S-V2 — Pylontech Force-H2-V2 Operation Manual V1.0
FC0500M-40S-V2 — KOSTAL DOC03306755 remark 'BMS module FC0500M-40S-V2 required'

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

Black start10-minute duration
Grounding resistancemust ≤100mΩ
Short circuit rating<4000 A
Standard charge / discharge current7.4 A
document_demoted_to_mirrorhttps://www.kostal-solar-electric.com/fileadmin/downloadcenter/kse/DB/PLENTICORE-G2/DB_PLENTICORE-plus_Tec-sheet-with-all-batteries_en.pdf
documented_relationship:inverter_battery{"to_manufacturer": "KOSTAL", "to_model": "PLENTICORE series", "relationship_type": "inverter_battery", "match_level": "series", "status": "compatible", "source": "Compatibility List of Pylontech High Voltage ESS and Inverters Ver.2.40 (2025-08-15)", "source_url": "https://solsol.eu/file/view/3679/pylontech_compatibility-list-of-pylontech-high-voltage-ess-and-inverters-ver.pdf", "source_page": "Footnote to the KOSTAL row", "confidence": "manufacturer-documented", "required_accessories": "UNKNOWN", "required_firmware": "UNKNOWN", "region": "GLOBAL", "notes": "Pylontech's own footnote: 'Only Force-H1-V2 and Force-H2-V2, Force-H3 are compatible with Kostal PLENTICORE series inverter'. Series-level."}
identity.product_statusUNKNOWN - no manufacturer document read states a lifecycle status; KOSTAL still lists it in a 07/2026 approved-battery sheet