SolaX Power T-BAT-SYS-HV-S3.6 (TP-HS36 stack)
Official manufacturer EU/global verified Sept. 1, 2026
UNKNOWN
Identity
| category | batteries |
| ean | UNKNOWN |
| generation | HS36 |
| manufacturer | SolaX Power |
| market_version | EN datasheet V1.9; user manual Version 16.0 |
| model | T-BAT-SYS-HV-S3.6 (TP-HS36 stack) |
| mpn | TP-HS36 |
| note | distinct from the already-recorded Triple Power T-BAT-SYS-HV 5.8 (T58): the HS36 line uses 3.6 kWh / 102.4 V modules with a TBMS-MCS0800 BMS and scales to 13 modules |
| product_family | T-BAT-SYS-HV-S2.5 (TP-HS25) / T-BAT-SYS-HV-S3.6 (TP-HS36) |
| product_status | active |
| region | EU/global |
| release_year | UNKNOWN |
| sku | TP-HS36 (module) |
Electrical
| chemistry | LFP (LiFePO4) |
| communication_can | True |
| communication_rs485 | True |
| firmware_requirements | BMS Software V2.01; Battery Module Software V2.01 (user manual) |
| max_continuous_charge_current_a |
35 (recommended) / 50 (maximum)
High-voltage Battery System T-BAT-SYS-HV-S3.6 7.37 kWh ~ 47.92 kWh Datasheet — 'Max continuous current: 35 A recommended / 50 A maximum'
|
| max_continuous_discharge_current_a | 35 (recommended) / 50 (maximum) |
| max_continuous_power_kw | UNKNOWN (not printed) |
| max_parallel_units | supported via multiple BMS units (count not stated in the fetched documents) |
| max_series_units | 13 total modules; maximum 10 per single tower - beyond 10 modules a Series Box is required to connect two towers in series |
| min_series_units_hv | 2 |
| nominal_energy_kwh | 7.37-47.92 (2-13 modules of 3.6 kWh) |
| nominal_voltage_v | 102.4 per TP-HS36 module; stack nominal = N x 102.4 (N = 2-13) |
| officially_supported_inverter_brands | ['SolaX Power'] |
| officially_supported_inverter_models | UNKNOWN (neither the datasheet V1.9 nor the user manual names inverter models; the manual only describes the BMS-to-inverter BAT+/BAT-/BMS port wiring) |
| peak_current_a | UNKNOWN (not printed) |
| supported_inverter_protocols | ['CAN2.0', 'RS485'] |
| usable_energy_kwh | 7.37-47.92 usable per datasheet headline (90 % DoD stated separately in the spec table) |
| voltage_class | HV |
| voltage_range_v | UNKNOWN per stack size. Datasheet V1.9 tabulates a 90-116 V d.c. window at module level; the manual quotes an overall system range of 90-750 V d.c. across all configurations |
Physical / mechanical
| bms_dimensions_mm | 510 x 157 x 365 |
| bms_weight_kg | 13 +/- 0.5 |
| cable_entry_positions | UNKNOWN |
| depth_mm | 365 |
| height_mm | stack height = 152 mm per module + 157 mm BMS + base |
| module_dimensions_mm | 510 x 152 x 365 |
| module_energy_kwh | 3.6 |
| module_nominal_voltage_v | 102.4 |
| module_weight_kg | 34 +/- 1 |
| mounting_bolt_size | expansion bolts, minimum diameter 10 mm, embedded depth >= 50 mm; M4x14 and M4x10 Phillips screws; M6 flange nuts |
| mounting_type | ['floor'] |
| terminal_locations | BAT+ / BAT- / BMS port on the TBMS-MCS0800 BMS unit |
| torque_specs |
M4x14 battery-mounting screws 0.9-1.1 N.m; M4x10 bracket screws 0.9-1.1 N.m; M6 flange nuts (bracket) 5 N.m; grounding terminal 4.5-5 N.m; self-tapping wall screws 4 N.m
T-BAT-SYS-HV-S2.5 / T-BAT-SYS-HV-S3.6 User Manual Version 16.0 — mechanical installation chapter, fastener torque table
|
| weight_kg | 34 (+/-1) per TP-HS36 module; 13 (+/-0.5) for the TBMS-MCS0800 BMS |
| width_mm | 510 |
Installation
| clearance_between_towers_mm | 400-800 |
| clearance_left_mm | 400 |
| clearance_rear_mm | 30-200 (60 recommended) |
| clearance_right_mm | 400 |
| clearance_top_mm | 100 |
| indoor_outdoor | indoor or outdoor (IP65); 'Avoid direct sunlight' |
| installation_humidity_range | 5-95 % RH |
| max_installation_altitude_m | 3000 |
| maximum_modules_per_stack |
10
T-BAT-SYS-HV-S2.5 / T-BAT-SYS-HV-S3.6 User Manual Version 16.0 — 'Maximum: 10 battery modules per single tower'
|
| maximum_stacks_in_parallel | UNKNOWN (parallel connection via multiple BMS units is supported) |
| minimum_modules_per_stack | 2 |
| mounting_orientation | upright tower on a base, secured to the wall with an L-bracket and adjustable bracket |
| orientation_allowed | ['floor tower with wall bracket'] |
| parallel_rules |
'If the battery module users purchased excesses 11 sets (including 11), a Series Box needs to be installed to connect two towers in series.' Maximum configuration 13 modules = 47.92 kWh.
T-BAT-SYS-HV-S2.5 / T-BAT-SYS-HV-S3.6 User Manual Version 16.0 — 'If the battery module users purchased excesses 11 sets (including 11), a Series Box needs to be installed to connect two towers in series.'
|
| seismic_anchoring | L-bracket + adjustable bracket with M6 flange nuts (5 N.m), expansion bolts >= 10 mm diameter and >= 50 mm depth |
| surface_requirements | 'the bearing capacity of the ground ... must be over 500 kg/m2' |
| two_person_lift_required | UNKNOWN (34 kg per module) |
Environment
| charge_temperature_c | -30 to +53 (with heating); charge current reduced 0 to +25 and +45 to +53 |
| cooling_method | natural convection with integrated heating film |
| discharge_temperature_c | -30 to +53 (with heating); discharge current reduced -20 to +10 and +45 to +53 |
| ik_rating | UNKNOWN |
| ip_rating | IP65 |
| max_altitude_m | 3000 |
| nema_rating | UNKNOWN |
| noise_level_db | UNKNOWN |
| operating_temperature_c | -30 to +53 with heating; -20 to +53 discharge without heating |
| relative_humidity | 4-100 % RH (datasheet); 5-95 % RH (manual) |
| storage_temperature_c | -20 to +30 (12 months); +30 to +50 (6 months) |
Interfaces & connectors
| battery_terminal_type | hot-plug power connectors with white lock buttons; DC cable 8.5-9.5 mm2 recommended at 50 A rated current; optional RNB14-5 ring terminals (10 mm2 grounding) and Phoenix male/female terminals |
| can | yes (CAN2.0) |
| dry_contacts | UNKNOWN |
| ethernet | no (RJ45 carries the BMS bus) |
| grounding | RNB5-6 terminal, 4-6 mm2 wire, heat-shrink tubing 28-30 mm |
| protocol_notes | RJ45 8-pin BMS bus: GND, GND, BMS_H, BMS_L, 12V, A1, B1. DIP switch 4 sets the terminating resistor: open (down) for a single BMS or the last unit in a parallel chain, closed (up) for non-terminal parallel BMS units. Shielded cable required. |
| rs485 | yes |
Controls & display
| audible_alarm | UNKNOWN |
| buttons | POWER button (>0.5 s start, >1 s shutdown, >5 s inverter startup mode, >20 s black start) and a rotary SWITCH (ON/OFF, lockable variant with ON/OFF/OFF+LOCK key lock) |
| display_type | none (LED indicators only) |
| leds | status indicator (solid green normal, solid red fault for >=10 min then 1 s on / 4 s off, yellow flash warning) plus four SOC indicators SOC1-SOC4 |
| local_display | False |
| mobile_app | SolaX Cloud / SolaXCloud app (via inverter) |
| touchscreen | False |
Protection
| fire_guidance | 'keep a Class ABC fire extinguisher or a carbon dioxide extinguisher near the equipment'; 'If the battery module catches fire, please do not try to put out the fire, and evacuate immediately.' |
| integrated_breakers_fuses |
integrated DC fuse - 'Component Type DC Fuse; Fuse Type EV / HEV; Rated Voltage 750 Vdc/Vac; Rated Current 60 A'
T-BAT-SYS-HV-S2.5 / T-BAT-SYS-HV-S3.6 User Manual Version 16.0 — DC fuse specification table, 750 Vdc / 60 A
|
| integrated_dc_switch | rotary SWITCH on the BMS (not a breaker) |
| over_current | yes (BMS_ChargeOverCurrent / BMS_DischargeOverCurrent faults at the 50 A limit) |
| over_temperature | yes (BMS_TemHigh / BMS_TemLow, with current derating bands) |
| over_voltage | yes (single-cell overvoltage monitoring) |
| short_circuit | yes (DC fuse) |
| thermal_runaway_measures | 'Do not dispose of the battery module in a fire'; 'The battery module may catch fire when heated above 302 F' |
| under_voltage | yes |
Certifications
| emc | [] |
| grid_codes | [] |
| other | ['UN38.3', 'UL9540A'] |
| regional | ['CE'] |
| safety | ['IEC62619', 'IEC60730', 'IEC62040'] |
Warranty & service
| conditions | recharge at least once every 12 months when stored at -20 to +30 C, or every 6 months at +30 to +50 C; minimum 50 % SOC if unused for more than 9 months |
| cycle_life | > 6000 cycles |
| design_life_years | UNKNOWN |
| standard_years | UNKNOWN (not printed on datasheet V1.9 or the official product page) |
| throughput_guarantee_mwh | UNKNOWN |
Packaging & logistics
| gross_weight_kg | UNKNOWN |
| transport_restrictions |
'UN number UN 3480; Hazardous materials classification Class 9; UN transportation testing requirements UN 38.3'
T-BAT-SYS-HV-S2.5 / T-BAT-SYS-HV-S3.6 User Manual Version 16.0 — transport chapter, UN 3480 / Class 9 / UN 38.3
|
Documents
Additional documented parameters
Recorded verbatim from the source; no schema field exists for these yet.
| Black start | POWER button held > 20 s |
| DC fuse | EV/HEV type, 750 Vdc/Vac, 60 A |
| DIP switch 4 (terminating resistor) | open for single/last BMS, closed for non-terminal parallel BMS |
| Ground bearing capacity | must be over 500 kg/m2 |
| Series Box | required for >= 11 modules to series-connect two towers |