⚡ANMASystem BuildingAutomation, Network, Monitoring & Analytics
★PREMIUM

Knowledge Base › Current Transformers (CT)

Official manufacturer EU verified Sept. 25, 2026

Identity

category current_transformers
manufacturer Frer
model TAT0611K0X33
product_status active
region EU
variant —

Electrical

accuracy_class 1
FRER 333mV output measuring CT data sheet (TAC022 / TAC040 / TAT061)
aperture_mm 51
FRER 333mV output measuring CT data sheet (TAC022 / TAC040 / TAT061)
bidirectional True
continuous_overcurrent 100% Ipr
FRER 333mV output measuring CT data sheet (TAC022 / TAC040 / TAT061)
ct_type solid_core
FRER 333mV output measuring CT data sheet (TAC022 / TAC040 / TAT061)
frequency_hz 50-60
FRER 333mV output measuring CT data sheet (TAC022 / TAC040 / TAT061)
housing self-extinguishing thermoplastic UL94-V0
FRER 333mV output measuring CT data sheet (TAC022 / TAC040 / TAT061)
insulation_class E
FRER 333mV output measuring CT data sheet (TAC022 / TAC040 / TAT061)
insulation_voltage_v 0.72 kV
max_current_a 65.0
measurement_type Current Transformer (CT)
phase_count 1
primary_current_a 1000
FRER 333mV output measuring CT data sheet (TAC022 / TAC040 / TAT061)
rated_dynamic_current 2,5 x I th
FRER 333mV output measuring CT data sheet (TAC022 / TAC040 / TAT061)
rated_insulation_voltage_v 720
FRER 333mV output measuring CT data sheet (TAC022 / TAC040 / TAT061)
rated_short_time_thermal_current < 40 x Ipr (max. 90kA/1s)
FRER 333mV output measuring CT data sheet (TAC022 / TAC040 / TAT061)
ratio 1000A/333mV
FRER 333mV output measuring CT data sheet (TAC022 / TAC040 / TAT061)
secondary_voltage_mv 333
FRER 333mV output measuring CT data sheet (TAC022 / TAC040 / TAT061)
test_voltage 3 kV x 1' 50 Hz
FRER 333mV output measuring CT data sheet (TAC022 / TAC040 / TAT061)
voltage_rating_v 230.0
window_diameter_mm 61 x 31 (busbar) or 51 (cable, diameter)
window_size 61x31 Busbar or D51 Cable passing
FRER 333mV output measuring CT data sheet (TAC022 / TAC040 / TAT061)

Physical / mechanical

mounting DIN-rail
weight_kg 0.50 to 1.00

Environment

ip_rating IP00 (IP20 with terminal covers)
FRER 333mV output measuring CT data sheet (TAC022 / TAC040 / TAT061)
operating_temperature_max_c 50
FRER 333mV output measuring CT data sheet (TAC022 / TAC040 / TAT061)
operating_temperature_min_c -25
FRER 333mV output measuring CT data sheet (TAC022 / TAC040 / TAT061)
operating_temperature_range_c -25 to +50
storage_temperature_range_c -40 to +80

Interfaces & connectors

communication RS485 Modbus RTU

Protection

protection_degree_ip IP 00 (IP 20 with terminal covers fitted)

Certifications

certifications IEC/EN 61869-1, IEC/EN 61869-10
standards ['IEC/EN 61869-1', 'IEC/EN 61869-10']
FRER 333mV output measuring CT data sheet (TAC022 / TAC040 / TAT061)

Documents

certificate FRER 333mV output measuring CT certifications
datasheet FRER 333mV output measuring CT data sheet (TAC022 / TAC040 / TAT061)
product_page Busbar or Cable passing measuring CTs 333mV output

Recorded conflicts

electrical.test_voltage Resolved — kept current value
3 kV x 1' 50 Hz — stored value
3 kV for 1 min at 50 Hz — incoming package
Detected during import deep-enrich-pass2-2026-09-batch10
electrical.frequency_hz Resolved — kept current value
50-60 — stored value
50 to 60 — incoming package
Detected during import deep-enrich-pass2-2026-09-batch10

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

builder_completenesscomplete
region_notesItalian manufacturer; IEC/EN 61869 measuring CT for the European market.