Knowledge Base › Current Transformers (CT)
Omron KM-PCBE600
Official manufacturer GLOBAL verified Sept. 25, 2026
Identity
| category | current_transformers |
| manufacturer | Omron |
| model | KM-PCBE600 |
| product_status | active |
| region | GLOBAL |
| variant | — |
Electrical
| accuracy_class | Class 1.0 |
| allowable_attach_detach_cycles | 100 |
| allowable_attachment_cycles |
100
KM-PM Power Monitor / Specifications
|
| bidirectional | True |
| cable_length_m |
2.9
KM-PM Power Monitor / Specifications
|
| cable_terminals | Ferrule terminal (Output side); round terminal (CT side) |
| compatible_meter_models |
['KM-PMBN-EIP']
KM-PM Power Monitor / Specifications
|
| ct_output_terminal |
Ferrule terminal
KM-PM Power Monitor / Specifications
|
| ct_side_terminal |
Round terminal
KM-PM Power Monitor / Specifications
|
| dielectric_strength_v | 2,000 VAC for 1 minute (between output terminals and case) |
| dielectric_strength_vac |
2000
KM-PM Power Monitor / Specifications
|
| insulation_resistance | 50 M-ohm min. between output terminals and case (printed on the page as '50 m-ohm min.'; the lower-case prefix is an evident typo in Omron's HTML, the value is reproduced here as the megohm figure Omron uses for the same row on its other CT pages - treat with care) |
| insulation_resistance_mohm |
50
KM-PM Power Monitor / Specifications
|
| lead_length_m | 2.9 |
| max_current_a | 100.0 |
| measurement_type | Current Transformer (CT) |
| official_product_url |
https://www.ia.omron.com/products/family/3955/lineup.html
KM-PM Power Monitor / Lineup — inventory record source_url
|
| operating_humidity_pct_rh | 25% to 85% RH (with no icing or condensation) |
| phase_count | 1 |
| primary_current_a |
600
KM-PM Power Monitor / Lineup
|
| protective_element |
7.5 V clamp element
KM-PM Power Monitor / Specifications
|
| rated_voltage_v |
480
KM-PM Power Monitor / Specifications
|
| secondary_output | 9,000 turns |
| secondary_winding_turns |
9000
KM-PM Power Monitor / Specifications
|
| storage_humidity_pct_rh | 25% to 85% RH (with no icing or condensation) |
| voltage_rating_v | 230.0 |
Environment
| operating_temperature_max_c |
55
KM-PM Power Monitor / Specifications
|
| operating_temperature_min_c |
-25
KM-PM Power Monitor / Specifications
|
| operating_temperature_range_c | -25 to 55 |
| storage_temperature_max_c |
65
KM-PM Power Monitor / Specifications
|
| storage_temperature_min_c |
-30
KM-PM Power Monitor / Specifications
|
| storage_temperature_range_c | -30 to 65 |
Certifications
| certifications | None - Omron states the 600 A rating does not support safety standard certification, including UL/CSA certification |
Documents
product_page
KM-PM Power Monitor / Lineup
product_page
KM-PM Power Monitor / Specifications
Additional documented parameters
Recorded verbatim from the source; no schema field exists for these yet.
| builder_completeness | partial |
| region_notes | OMRON's English-language industrial-automation catalogue (ia.omron.com) is the source; OMRON is a Japanese manufacturer and uses the same designation worldwide. |