ANMASystem BuildingAutomation, Network, Monitoring & Analytics
PREMIUM

Knowledge BaseData Loggers

Sungrow Logger1000B

Official manufacturer GLOBAL verified Sept. 3, 2026

Identity

category data_loggers
device_type PV plant data logger / communication and control unit
manufacturer Sungrow
model Logger1000B
note Recorded separately from Logger1000A: its own datasheet (V13) states three RS485 channels and does not state 4G bands.
product_family Logger1000
product_name Logger1000B
region GLOBAL

Electrical

dc_output 24 VDC, 0.5 A
power_consumption < 10 W
power_supply 24 VDC, 1.2 A input

Physical / mechanical

dimensions_w_h_d_mm 200 x 110 x 60
mounting Top-hat rail mounting / wall mounting
weight_kg 0.5

Installation

cloud_vs_local Local web monitoring plus FTP/SFTP push and cloud upload
commissioning Built-in web server for monitoring and configuration from a browser (family product page)
max_supported_devices 30
topology RS485 bus to inverters/meters/sensors; upstream Ethernet or WLAN

Environment

humidity <= 95 % non-condensing
max_altitude_m 4000
operating_temperature_c -30 to 60
storage_temperature_c -40 to 70

Interfaces & connectors

analog_inputs 4, 4 mA - 20 mA or 0 VDC - 10 VDC
cellular_4g UNKNOWN - not stated in the Logger1000B datasheet
digital_inputs 5, max 24 VDC
digital_outputs UNKNOWN
ethernet 1 x RJ45, 10/100/1000 Mbps
protocols_northbound Modbus-TCP, IEC 60870-5-104, FTP / SFTP (over Ethernet)
protocols_southbound Modbus-RTU, DL/T645 (over RS485)
register_map_availability UNKNOWN
rs485_channels 3
wlan 802.11 b / g / n / ac, 2.4 GHz / 5 GHz

Protection

ip_rating IP20

Documents

compatibility_list COMPATIBILITY LIST PUBLIC 2026 | VERSION 4.3 rev 4.3
datasheet Logger1000B Datasheet rev V13
product_page Logger1000A / Logger1000B product page (sungrowpower.com) rev UNKNOWN
quick_installation_guide {# Located but never retrieved: listed, but deliberately not linked, and it backs no stored value. #} Logger1000A/B Quick Installation Guide — located, not retrieved rev UNKNOWN
user_manual {# Located but never retrieved: listed, but deliberately not linked, and it backs no stored value. #} Logger1000A/B User Manual — located, not retrieved rev UNKNOWN

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

documented_relationship:inverter_gateway{"to_manufacturer": "Sungrow", "to_model": "SG2.0-6.0RS; SG3.0-20RT; SHxxT; C&I inverter series", "relationship_type": "inverter_gateway", "match_level": "series", "communication_protocol": "RS485 / Modbus-RTU", "required_firmware": "UNKNOWN", "required_settings": "UNKNOWN", "required_accessories": "UNKNOWN", "region": "EU", "source": "COMPATIBILITY LIST PUBLIC 2026 | VERSION 4.3", "source_url": "https://info-support.sungrowpower.com/market-material/41ab25da-0bbb-451b-8a51-fd4abd3be0bd.pdf", "source_page": "UNKNOWN", "confidence": "manufacturer-documented", "status": "COMPATIBLE", "notes": "The compatibility list prints \"Logger1000\" and \"Logger1000A-EU\" rows; it does not print a Logger1000B row in the extracts obtained. This row is therefore recorded at series level against the Logger1000 family and flagged as such - do not treat it as a Logger1000B-specific statement."}
manufacturer_legal_entity_as_printedSungrow Power Supply Co., Ltd.

Build a system with this product