⚡ANMASystem BuildingAutomation, Network, Monitoring & Analytics
★PREMIUM

Knowledge Base › Gateways / Data Loggers

Enphase ENV2-IQ-AM1-240

Official manufacturer NA verified Sept. 22, 2026

Identity

category gateways
ean —
firmware {'documented_version': 'UNKNOWN', 'constraints': 'UNKNOWN'}
generation —
manufacturer Enphase
market_version North America 120/240 V, 120/208Y V or 127/220Y V, 60 Hz
model ENV2-IQ-AM1-240
mpn ENV2-IQ-AM1-240
product_family IQ Gateway
product_status active
region NA
release_year —
series IQ Gateway
sku ENV2-IQ-AM1-240

Electrical

metering_accuracy Revenue-grade PV production metering (ANSI C12.20 +/-0.5%); consumption metering (+/-2.5%); battery metering (+/-2.5%)
microinverters_supported Up to 300
nominal_ac_voltage 120/240 V, 120/208Y V, or 127/220Y V. Three-wire. 60 Hz
nominal_frequency_hz 60
official_product_url https://enphase.com/store/communication/iq-gateway-ieee-certified
Enphase IQ Gateway (IEEE Certified) - SKU ENV2-IQ-AM1-240
overcurrent_protection 2-pole, maximum 20 A
power_consumption_w Typical 5 W
supply_voltage 100-240 V AC

Physical / mechanical

cooling —
depth_mm 45
dimensions_mm 213 x 126 x 45
display —
enclosure_material —
height_mm 213
mounting Aluminium DIN rail 124.46 mm
noise_db —
weight_kg 0.5
width_mm 126

Environment

ingress_protection IP30 - indoors, or in an NRTL-certified NEMA type 3R or better enclosure outdoors
ip_rating IP20
max_altitude_m 3000
operating_temperature_c -40 to 50 (-40 to 46 if installed in an enclosure)
operating_temperature_max_c 60.0
operating_temperature_min_c -25.0
overvoltage_category —
pollution_degree —
protective_class —
relative_humidity_pct —
storage_temperature_c —

Interfaces & connectors

app Enphase App
communication ['Wi-Fi 802.11 b/g/n (2.4 GHz, 5 GHz)', 'Ethernet 802.3 Cat5E/Cat6', 'Power line communication 90 kHz-110 kHz (Class B) to microinverters', 'Optional cellular (Mobile Connect)', 'Access Point (AP) mode']
dry_contact —
interfaces RS485, Ethernet, Wi-Fi
meter_interface One 200 A Production CT included
monitoring_portal Enphase Installer Platform / Enphase App
protocols ['IEEE 2030.5', 'Web API', 'Local API']
supported_devices_max 32

Certifications

standards ['CSIP (IEEE 2030.5)', 'CAN/CSA C22.2 No. 61010-1', 'Title 47 CFR Part 15 Class B', 'ICES 003', 'IEC/UL 61010-1:2010', 'ANSI C12.20 accuracy class 0.5 (metering)']

Warranty & service

conditions 5-year limited warranty
extension_options —
standard_years 5

Documents

datasheet IQ Gateway Data Sheet rev DSH-00111-6.0-EN-2025-06-06
product_page Enphase IQ Gateway (IEEE Certified) - SKU ENV2-IQ-AM1-240

Recorded conflicts

max_microinverters Review required
300 —
600 —

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

documented_relationship:inverter_gateway{"to_manufacturer": "Enphase", "to_model": "IQ6, IQ7 and IQ8 Series microinverters", "relationship_type": "inverter_gateway", "match_level": "series", "status": "compatible", "source": "IQ Gateway Data Sheet", "source_url": "https://enphase.com/download/iq-gateway-data-sheet", "source_page": "Compatibility", "confidence": "officially-verified", "required_accessories": "", "required_firmware": "", "region": "NA", "notes": ""}