⚡ANMASystem BuildingAutomation, Network, Monitoring & Analytics
★PREMIUM

Knowledge Base › Inverters

EG4 EG4 FlexBOSS21

Official manufacturer NA verified Sept. 25, 2026

Unresolved safety-relevant conflict
Two sources give different figures for a value on this product and nobody has resolved it. The specifications below are shown as recorded, but this product must not be treated as verified for engineering purposes until the conflict is closed.

Identity

category inverters
ean —
firmware {'documented_version': 'UNKNOWN', 'constraints': 'UNKNOWN'}
generation —
manufacturer EG4
market_version NA (UL 1741 / split-phase 120/240 VAC)
model EG4 FlexBOSS21
mpn IV-16000-HYB-AW-FX-XX
product_family FlexBOSS
product_status —
region —
release_year —
series FlexBOSS
sku IV-16000-HYB-AW-FX-XX

Electrical

ac_connection 1ø
ac_voltage_range —
battery_capacity_range_kwh —
battery_communication —
battery_max_charge_current_a 250
battery_max_charge_power_w —
battery_max_discharge_current_a 250
battery_max_discharge_power_w —
battery_nominal_battery_voltage_v 51.2
battery_nominal_voltage_v 51.2
EG4 FlexBOSS21 Hybrid Inverter Spec Sheet
battery_supported True
EG4 FlexBOSS21 Hybrid Inverter Spec Sheet
battery_type —
battery_voltage_max_v 60
EG4 FlexBOSS21 Hybrid Inverter Spec Sheet
battery_voltage_min_v 40
EG4 FlexBOSS21 Hybrid Inverter Spec Sheet
battery_voltage_range_v 40 - 60 VDC
cec_weighted_efficiency_pct 97
eps_peak_power 24000W (.5 sec) | 18000W (1 sec) | 15000W (6 min) | 13200W (12 min)
eps_phase —
eps_rated_power_va —
eps_switchover_time_ms 20ms (Default), 10ms (Configurable)
eps_voltage —
european_efficiency_pct —
external_transfer_switch_required —
frequency_range_hz 50/60Hz
inrush_current —
max_ac_active_power_w 16kW (rated continuous); 12kW (battery only)
max_ac_current_a 66.7
max_ac_power_w 16000
EG4 FlexBOSS21 Hybrid Inverter Spec Sheet
max_apparent_power_va 16000
max_backfeed_current_a —
max_charge_current_a 250
EG4 FlexBOSS21 Hybrid Inverter Spec Sheet
max_dc_input_power_w 21000
max_dc_voltage_v 600
max_discharge_current_a 250
EG4 FlexBOSS21 Hybrid Inverter Spec Sheet
max_efficiency_pct 97
max_input_current_per_mppt_a 26A (MPPT 1) | 26A (MPPT 2) | 15A (MPPT 3) disputed
max_output_fault_current_a —
max_pass_through_current_a 90
max_pv_input_voltage_v 600
EG4 FlexBOSS21 Hybrid Inverter Spec Sheet
max_short_circuit_current_per_mppt_a 31A (MPPT 1) | 31A (MPPT 2) | 19A (MPPT 3) disputed
mppt_efficiency_pct —
mppt_voltage_max_v 440
EG4 FlexBOSS21 Hybrid Inverter Spec Sheet
mppt_voltage_min_v 120
EG4 FlexBOSS21 Hybrid Inverter Spec Sheet
mppt_voltage_range_v 250 - 440 VDC (full power)
night_self_consumption_w —
nominal_ac_voltage 120/240 or 208 VAC
nominal_dc_voltage_v —
nominal_frequency_hz —
nominal_grid_voltage_v ['120/240', '120/208']
EG4 FlexBOSS21 Hybrid Inverter Spec Sheet
number_of_mppt 3
EG4 FlexBOSS21 Hybrid Inverter Spec Sheet
official_manual_url https://eg4electronics.com/wp-content/uploads/2024/08/FlexBOSS-21-Manual.pdf
EG4 FlexBOSS21 product page
official_product_url https://eg4electronics.com/categories/inverters/eg4-flexboss-21/
EG4 FlexBOSS21 product page
parallel_capability 16
phase_count 1
EG4 FlexBOSS21 Hybrid Inverter Spec Sheet
power_factor_range —
product_status active
EG4 FlexBOSS21 product page
rated_ac_power_w 16000
rated_mppt_voltage_range_v —
startup_voltage_v 200
EG4 FlexBOSS21 Hybrid Inverter Spec Sheet
strings_per_mppt 2 (MPPT 1) / 2 (MPPT 2) / 1 (MPPT 3)
strings_per_mppt_distribution [2, 2, 1]
EG4 FlexBOSS21 Hybrid Inverter Spec Sheet
thd_pct —

Physical / mechanical

ac_terminal —
cooling —
dc_connector —
depth_mm 285
dimensions_mm 773 x 566 x 285
display —
enclosure_material —
height_mm 773
mounting —
noise_db —
weight_kg 55
width_mm 566

Installation

cable_requirements —
commissioning —
installation_angle —
mounting_clearances —
torque —

Environment

ingress_protection NEMA 4X
max_altitude_m —
operating_temperature_c -25° - 60°C
pollution_degree —
protective_class —
relative_humidity_pct —
storage_temperature_c —

Interfaces & connectors

app —
communication ['Wi-Fi', 'Cellular', 'Ethernet']
dry_contact —
meter_interface —
monitoring_portal —
protocols []

Protection

anti_islanding —
arc_fault —
dc_switch —
insulation_monitoring —
overvoltage_category —
rcmu —
reverse_polarity —
surge_protection_ac —
surge_protection_dc —

Warranty & service

conditions —
extension_options —
standard_years 10

Documents

datasheet EG4 FlexBOSS21 Hybrid Inverter Spec Sheet rev UNKNOWN
installation_manual EG4 FlexBOSS21 Hybrid Inverter User Manual, Version 1.3.7 (model IV-16000-HYB-AW-FX-XX)
product_page EG4 FlexBOSS21 product page

Recorded conflicts

electrical.max_short_circuit_current_per_mppt_a Review required
31A (MPPT 1) | 31A (MPPT 2) | 19A (MPPT 3) — stored value
[31, 31, 19] — SHORT-CIRCUIT CURRENT RATING PER MPPT 31A (MPPT 1) | 31A (MPPT 2) | 19A (MPPT 3) — axis: MPPT
Detected during import v1-freeze-2026-09-batch07
electrical.max_input_current_per_mppt_a Review required
26A (MPPT 1) | 26A (MPPT 2) | 15A (MPPT 3) — stored value
[26, 26, 15] — RATED CURRENT PER MPPT 26A (MPPT 1) | 26A (MPPT 2) | 15A (MPPT 3) — axis: MPPT
Detected during import v1-freeze-2026-09-batch07
electrical.max_ac_current_a Resolved — accepted incoming value
66.7A (rated continuous) | 50A (battery only) — stored value
66.7 — MAX. CONTINUOUS OUTPUT 66.7A | 16kW
Detected during import v1-freeze-2026-09-batch07

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

CEC WEIGHTED EFFICIENCY97%
MAX. APPARENT POWER WITH BATTERY12kVA
NOMINAL VOLTAGE51.2 VDC
RATED CURRENT PER MPPT26A (MPPT 1) | 26A (MPPT 2) | 15A (MPPT 3)
SHORT-CIRCUIT CURRENT RATING PER MPPT31A (MPPT 1) | 31A (MPPT 2) | 19A (MPPT 3)
battery.communicationUNKNOWN
battery.max_charge_current_a250
battery.max_charge_power_wUNKNOWN
battery.max_discharge_current_a250
battery.max_discharge_power_wUNKNOWN
battery.nominal_battery_voltage_v51.2
builder_completenesspartial