⚡ANMASystem BuildingAutomation, Network, Monitoring & Analytics
★PREMIUM

Knowledge Base › Inverters

Fronius Primo GEN24 4.0 Plus

Official manufacturer GLOBAL verified Sept. 25, 2026

Unresolved safety-relevant conflict
Two sources give different figures for a value on this product and nobody has resolved it. The specifications below are shown as recorded, but this product must not be treated as verified for engineering purposes until the conflict is closed.

Identity

brand Fronius
category inverters
ean —
firmware {'documented_version': 'UNKNOWN', 'constraints': 'UNKNOWN'}
generation GEN24
manufacturer Fronius
manufacturer_key fronius
market_version —
model Primo GEN24 4.0 Plus
model_key primogen2440plus
mpn —
product_family Primo GEN24 Plus
product_status active
region GLOBAL
release_year —
series Primo GEN24 Plus
sku —

Electrical

ac_connection —
ac_voltage_range —
battery_capacity_range_kwh —
battery_communication —
battery_max_charge_current_a 22
battery_max_charge_power_w 4140 W
battery_max_discharge_current_a —
battery_max_discharge_power_w 4140 W
battery_nominal_battery_voltage_v —
battery_type —
battery_voltage_range_v 150 V - 455 V
eps_peak_power —
eps_phase —
eps_rated_power_va —
eps_switchover_time_ms —
eps_voltage —
european_efficiency_pct 95.8 / 97.1 / 96.5 (210Vdc / 400Vdc / 530Vdc)
external_transfer_switch_required —
frequency_range_hz —
inrush_current —
max_ac_active_power_w —
max_ac_current_a 25,8 A
max_ac_power_va 4000
Fronius help-center technical data - Fronius Primo GEN24 4.0 Plus
max_apparent_power_va 4000
max_backfeed_current_a —
max_dc_input_power_w 6 kWpeak
max_dc_voltage_v 600
max_efficiency_pct 97,6
max_input_current_per_mppt_a 22 / 12 A disputed
max_output_fault_current_a —
max_pv_input_voltage_v 600
Fronius help-center technical data - Fronius Primo GEN24 4.0 Plus
max_short_circuit_current_per_mppt_a 41,25 / 22 A disputed
mppt_efficiency_pct —
mppt_voltage_max_v 530
Fronius help-center technical data - Fronius Primo GEN24 4.0 Plus
mppt_voltage_min_v 210
Fronius help-center technical data - Fronius Primo GEN24 4.0 Plus
mppt_voltage_range_v 210 - 530 V
night_self_consumption_w <10
nominal_ac_voltage 1~ NPE 220/230 V
nominal_dc_voltage_v 400
nominal_frequency_hz 50 / 60
nominal_grid_voltage_v 230
Fronius help-center technical data - Fronius Primo GEN24 4.0 Plus
number_of_mppt 2
parallel_capability —
phase_count 1
Fronius help-center technical data - Fronius Primo GEN24 4.0 Plus
power_factor_range 0,8 - 1 ind./cap.
rated_ac_power_w 4000
Fronius help-center technical data - Fronius Primo GEN24 4.0 Plus
rated_mppt_voltage_range_v —
startup_voltage_v 80
strings_per_mppt 2+2
thd_pct —

Physical / mechanical

ac_terminal —
cooling —
dc_connector —
depth_mm 165.0
dimensions_mm 474 x 530 x 165
display —
enclosure_material —
height_mm 530.0
mounting —
noise_db —
weight_kg 15,38
width_mm 474.0

Installation

cable_requirements —
commissioning —
installation_angle —
mounting_clearances —
torque —

Environment

ingress_protection IP66
max_altitude_m —
operating_temperature_c -40°C - +60°C
pollution_degree —
protective_class 1
relative_humidity_pct 0 - 100 %
storage_temperature_c —

Interfaces & connectors

app —
communication [] disputed
dry_contact —
meter_interface —
monitoring_portal —
protocols []

Protection

anti_islanding —
arc_fault —
dc_switch —
insulation_monitoring —
overvoltage_category —
rcmu —
reverse_polarity —
surge_protection_ac —
surge_protection_dc —

Certifications

standards ['IEC 62109', 'IEC 62909', 'AS/NZS 4777.2', 'CEI 0-21', 'ABNT BNR 16149']

Warranty & service

conditions —
extension_options —
standard_years —

Documents

datasheet Fronius Primo GEN24 & GEN24 Plus 3.0 - 6.0 kW datasheet (EN)
product-page Fronius help-center technical data - Fronius Primo GEN24 4.0 Plus rev UNKNOWN
user-manual {# Located but never retrieved: listed, but deliberately not linked, and it backs no stored value. #} Fronius Primo GEN24 Plus operating instructions (linked from the technical-data page) — located, not retrieved rev UNKNOWN

Recorded conflicts

electrical.max_short_circuit_current_per_mppt_a Review required
41,25 / 22 A — stored value
[41.25, 22] — Max. short circuit current, module array | 41,25 / 22 A (MPPT1 / MPPT2)
Detected during import v1-freeze-2026-09-batch07
electrical.max_input_current_per_mppt_a Review required
22 / 12 A — stored value
[22, 12] — Max. input current (Idc max) | 22 / 12 A - two slash-separated values on one row for the two MPP trackers (MPPT1 / MPPT2); the page also prints 'Number of MPP trackers | 2'
Detected during import v1-freeze-2026-09-batch07
electrical.startup_voltage_v Resolved — accepted incoming value
80 V — stored value
80 — Feed-in start voltage (Udc start) | 80 V
Detected during import v1-freeze-2026-09-batch07
interfaces.communication Review required
[] — stored value
['WLAN', '2x Ethernet LAN', '2x RS485', '6x digital in/out + 6x digital in'] — incoming package
Detected during import wave8-saturation-2026-09-batch04

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

Battery Connection - Max. input current (Idc max.)22 A
Dimension / length165 mm
Max. input current (Idc max)22 / 12 A
Max. short circuit current, module array41,25 / 22 A
Max. switchover time PV-Point / Max. switchover time Full Backup15 s / 10 s
Output Data PV Point - Max continuous output power3000 VA
Usable MPP voltage range65 - 530 V
battery.communicationUNKNOWN
battery.max_charge_current_aUNKNOWN
battery.max_charge_power_w4140 W
battery.max_discharge_current_aUNKNOWN
battery.max_discharge_power_w4140 W
battery.nominal_battery_voltage_vUNKNOWN
builder_completenesspartial
withheld:pv.strings_per_mppt2