Fronius Primo GEN24 5.0 Plus

Official manufacturer UK/EU verified Sept. 1, 2026

Identity

brand Fronius
category inverters
ean UNKNOWN
generation GEN24
manufacturer Fronius International GmbH
market_version UK page (en-gb/uk) of fronius.com; the equivalent AU page carries the same electrical figures. Certificate list on the UK page includes AS/NZS 4777.2 and ABNT NBR (global certificate list).
model Primo GEN24 5.0 Plus
mpn UNKNOWN
product_family Fronius Primo GEN24 Plus 3.0 / 3.6 / 4.0 / 4.6 / 5.0 / 6.0
product_revision UNKNOWN
product_status active
region UK/EU
release_year UNKNOWN
sku UNKNOWN

Electrical

ac_coupling_support True
backup_eps_output_support True
battery_support True
battery_type HV lithium: BYD Battery-Box Premium HVS/HVM and LG RESU FLEX (with model exclusions, see officially_supported_battery_brands)
battery_voltage_class HV
battery_voltage_max_v 455
battery_voltage_min_v 150
Fronius Primo GEN24 5.0 Plus - Technical Data (HTML) — Technical Data > Battery Connection, 'DC input voltage range (Udc min - Udc max)' = '150 V - 455 V'; footnote 7 'An AC power derating of the inverter occurs from a battery DC input voltage of 419.7 V'
communication_can UNKNOWN
communication_ethernet True
communication_rs485 True
communication_wifi True
ct_support UNKNOWN
generator_input_support UNKNOWN
grid_certifications ['IEC 62109', 'IEC 62109-1', 'IEC 62109-2', 'IEC 62909', 'IEC 62116', 'IEC 61727', 'IEC 62477-1', 'IEC 62920', 'IEC 62368-1', 'EN 50549-1 (RfG)', 'AS/NZS 4777.2', 'CEI 0-21', 'ABNT NBR 16149', 'ABNT NBR 16150']
grid_export_control True
home_assistant_integration UNKNOWN
max_ac_power_kw 5
max_battery_charge_current_a 22
max_battery_charge_power_kw 5.17
max_battery_discharge_current_a 22
max_dc_voltage_v 600
Fronius Primo GEN24 5.0 Plus - Technical Data (HTML) — Technical Data > Input Data, 'DC input voltage range (Udc min - Udc max)' = '65 - 600 V'
max_input_current_per_mppt_a 22 (MPPT1) / 12 (MPPT2) - asymmetric
Fronius Primo GEN24 5.0 Plus - Technical Data (HTML) — Technical Data > Input Data, 'Max. input current (Idc max)' = '22 / 12 A'
max_pv_input_power_w 7500
max_short_circuit_current_per_mppt_a 41.25 (MPPT1) / 22 (MPPT2) - this is Isc max per the page footnote 'Isc pv = Isc max >= Isc (STC) x 1,25'; the Fronius Quick Start Guide states the un-multiplied module-array Isc as 33 A (MPPT1) / 18 A (MPPT2) - see data_conflicts
Fronius Primo GEN24 5.0 Plus - Technical Data (HTML) — Technical Data > Input Data, 'Max. short circuit current, module array*' = '41,25 / 22 A'; footnote '* Isc pv = Isc max >= Isc (STC) x 1,25'
modbus_rtu True
modbus_tcp True
mppt_max_voltage_v 530
mppt_min_voltage_v 230
num_mppt 2
officially_supported_battery_brands ['BYD Battery-Box Premium HVS (NOT HVS 10.2, NOT HVS 12.8)', 'BYD Battery-Box Premium HVM (NOT HVM 8.3, NOT HVM 22.1)', 'LG RESU FLEX (NOT RESU FLEX 17.2)']
Fronius Primo GEN24 5.0 Plus - Technical Data (HTML) — Technical Data > General Data, 'Compatible batteries' = 'BYD Battery-Box Premium HVS/HVM & LG RESU FLEX 5)' with footnote 5 listing the excluded models
phase_type single-phase
pv_inputs_per_mppt 2+2 (4 DC connections total; 2 per MPP tracker)
rated_ac_power_kw 5
smart_meter_support True
startup_voltage_v 80
sunspec_support True
topology hybrid

Physical / mechanical

bracket_dimensions_mm UNKNOWN
cable_entry_positions UNKNOWN
cable_gland_sizes UNKNOWN
depth_mm 165
diameter_mm UNKNOWN
din_rail_type UNKNOWN
enclosure_material UNKNOWN
height_mm 530
housing_color white (from product photograph on the official technical-data page)
mounting_bolt_size screws with thread diameter 6-8 mm (0.24-0.32 in); fixing material to be selected by the installer to suit the substrate
Fronius Primo GEN24 3 - 6 kW / 3 - 6 kW Plus / 3 - 6 kW SC / 3 - 6 kW SC Plus Operating instructions (HTML) — Installation > Installing the mounting bracket and attaching the inverter > Properties of the mounting bracket
mounting_hole_diameter_mm UNKNOWN
mounting_hole_spacing_mm 406 (distance from the left to the right pre-drilled hole of the mounting bracket)
Fronius Primo GEN24 3 - 6 kW / 3 - 6 kW Plus / 3 - 6 kW SC / 3 - 6 kW SC Plus Operating instructions (HTML) — Installation > Installing the mounting bracket and attaching the inverter > Properties of the mounting bracket
mounting_plate_dimensions_mm UNKNOWN
mounting_type ['wall', 'pole']
rack_units UNKNOWN
screw_sizes TX20 captive screws on the connection area cover
shipping_weight_kg 19
terminal_locations separate connection area behind the front cover (quick-fastener system)
torque_specs connection area cover quick-fastener system: screwdriver TX20, torque 0.5-5 N.m, do not turn the screws more than 180 degrees
Fronius Primo GEN24 3 - 6 kW / 3 - 6 kW Plus / 3 - 6 kW SC / 3 - 6 kW SC Plus Operating instructions (HTML) — Installation > General, 'Quick-fastener system'
weight_kg 15.38
Fronius Primo GEN24 5.0 Plus - Technical Data (HTML) — Technical Data > General Data, 'Weight' = '15,38 kg'
width_mm 474
Fronius Primo GEN24 5.0 Plus - Technical Data (HTML) — Technical Data > General Data, 'Dimension / width' = '474 mm'

Installation

altitude_derating_note The inverter must not be installed or operated at more than 4,000 m above sea level.
clearance_bottom_mm UNKNOWN
clearance_front_mm UNKNOWN
clearance_left_mm UNKNOWN (manual only states that ambient air must flow through the ventilation slots unimpeded; 2000 mm on all sides is required only for installation on the outer walls of cattle sheds)
clearance_right_mm UNKNOWN
clearance_top_mm UNKNOWN
cooling_airflow_requirements front air intake, side exhaust (thermal concept); ambient air must always flow through the ventilation slots unimpeded
direct_sunlight_restriction In order to keep inverter heating as low as possible, do not expose the inverter to direct sunlight. The inverter should be installed in a protected location, e.g. near the PV modules or under an overhanging roof.
indoor_outdoor indoor and outdoor installation (IP66)
installation_humidity_range 0-100 %
installation_temperature_range_c -40 to +60 (max. ambient temperatures stated in the installation-location chapter)
max_installation_altitude_m 4000
Fronius Primo GEN24 3 - 6 kW / 3 - 6 kW Plus / 3 - 6 kW SC / 3 - 6 kW SC Plus Operating instructions (HTML) — Installation > Installation location and position > Choosing the location of the inverter
minimum_wall_thickness_mm UNKNOWN
mounting_orientation vertical installation on a vertical wall or column; also permitted on a sloping surface with a minimum slope of the underside of 10 degrees
Fronius Primo GEN24 3 - 6 kW / 3 - 6 kW Plus / 3 - 6 kW SC / 3 - 6 kW SC Plus Operating instructions (HTML) — Installation > Installation location and position > Installation position of the inverter
orientation_allowed ['vertical on a vertical wall or column', 'sloping surface (min. slope of underside 10 degrees)']
orientation_forbidden ['sloping surface with the connections upwards', 'sloping position on a vertical wall or column', 'horizontal position on a vertical wall or column', 'connections upwards on a vertical wall or column', 'overhanging with the connections upwards', 'overhanging with the connections downwards', 'on the ceiling']
special_restrictions Do not install where the inverter may be exposed to ammonia, corrosive gases, acids or salts (fertilizer storage areas, vent openings for livestock stables, chemical plants, tanneries). Do not install in areas with an increased risk of accidents from farm animals, in stables or adjoining areas, or in storage areas for hay, straw, chaff, animal feed and fertilizers. Not to be installed in an occupied living area (slight operating noise). On outer walls of cattle sheds a minimum clearance of 2 m must be maintained between all sides of the inverter and the ventilation and building openings.
surface_requirements Only install on a solid, non-flammable surface. Permissible substrates: walls (corrugated metal walls with mounting rails, brick walls, concrete walls or other non-flammable surfaces sufficiently capable of bearing loads); mast or beam (installed using mounting rails, behind the PV modules on the PV mounting system); flat roofs (film roofs must comply with fire protection requirements and not be highly flammable); covered parking lot roofs (no overhead installation).
Fronius Primo GEN24 3 - 6 kW / 3 - 6 kW Plus / 3 - 6 kW SC / 3 - 6 kW SC Plus Operating instructions (HTML) — Installation > Installation location and position > Choosing the location of the inverter
two_person_lift_required UNKNOWN
ventilation_requirements When installing the inverter in a switch cabinet or similar closed environment, it is necessary to make sure that the hot air that develops will be dissipated by forced-air ventilation.

Environment

cooling_method regulated air cooling (active cooling with fan(s); fan test function in the inverter UI)
corrosion_class UNKNOWN
fan_replaceable yes (INFERRED: the operating instructions' Fan test function is described as a check 'for example after replacing a fan')
ik_rating UNKNOWN
ip_rating IP66
max_altitude_m 4000
nema_rating UNKNOWN
noise_level_db 42 dB(A)
Fronius Primo GEN24 5.0 Plus - Technical Data (HTML) — Technical Data > General Data, 'Sound emissions' = '42 dB(A)'
operating_temperature_c -40 to +60
pollution_degree UNKNOWN
relative_humidity 0-100 %
salt_mist_resistance UNKNOWN
storage_temperature_c UNKNOWN
uv_resistance UNKNOWN

Interfaces & connectors

ac_terminal_type 3-pole AC push-in spring terminals 2.5 - 10 mm2; 3-pole backup-power push-in spring terminals 1.5 - 10 mm2; 2x PE screw terminals 2.5 - 16 mm2 and 3x 2.5 - 10 mm2
analog_inputs UNKNOWN
auxiliary_power_output UNKNOWN
backup_eps_terminal 3-pole backup power push-in spring terminals 1.5 - 10 mm2
battery_terminal_type 1x BATT+ and 1x BATT- push-in spring terminals 2.5 - 10 mm2
bluetooth UNKNOWN
can UNKNOWN
cellular UNKNOWN
cloud_api Fronius Solar.web
digital_inputs 6x digital in/out + 6x digital in (interface to ripple control receiver, energy management)
dry_contacts UNKNOWN
ethernet 2x Ethernet LAN
generator_start_contact UNKNOWN
generator_terminal UNKNOWN
local_api Fronius Solar API (JSON)
modbus_rtu Modbus RTU SunSpec (via RS485)
modbus_tcp Modbus TCP SunSpec (via WLAN / Ethernet)
mqtt UNKNOWN
ocpp UNKNOWN
programmable_relay UNKNOWN
protocol_notes Datalogger and web server included as standard - no additional stick required. Open interfaces can be operated in parallel with Fronius Solar.web.
pv_connector_type 4x DC+ and 4x DC- push-in spring terminals 2.5 - 10 mm2
rapid_shutdown_interface emergency stop (WSD - wired shutdown): Yes
relay_outputs UNKNOWN
rs232 UNKNOWN
rs485 2x RS485 - Modbus RTU SunSpec (third-party supplier) / Fronius Smart Meter, battery, Fronius Ohmpilot
smart_load_output UNKNOWN
sunspec SunSpec over both Modbus RTU and Modbus TCP
usb UNKNOWN
wifi WLAN
zigbee UNKNOWN

Controls & display

audible_alarm UNKNOWN
buttons UNKNOWN
display_type none (web-based user interface)
leds UNKNOWN
local_display False
mobile_app Fronius Solar.web / Fronius Solar.start (UNKNOWN which exactly - not stated on the fetched page)
remote_display_option UNKNOWN
status_indicators UNKNOWN
touchscreen False
web_interface integrated web server / inverter user interface (Settings menu documented in the operating instructions)

Protection

afci UNKNOWN (not listed for Primo GEN24 Plus)
anti_islanding yes (IEC 62116 certified)
ground_fault_protection fast undervoltage / ground fault protection U<< configurable in backup power mode
insulation_monitoring DC insulation measurement: Yes (Exact / Fast modes, adjustable warning threshold 100,000 - 10,000,000 ohm)
integrated_breakers_fuses UNKNOWN
integrated_dc_switch True
over_current UNKNOWN
over_temperature overload behaviour: operating point shift, power limitation
over_voltage UNKNOWN
overvoltage_category 2 (DC) / 3 (AC), according to IEC 62109-1
protection_class 1
residual_current_monitoring continuous residual current monitoring, limit value adjustable 0.03 - 0.3 A; RCMU/FI false-trip mitigation settings
reverse_polarity DC reverse polarity protection: Yes
short_circuit backup-power short-circuit switch-off time configurable 0.001 - 60 s
surge_protection not integrated; optional retrofit DC SPD type 1+2 for 2 MPP trackers, Fronius item number 4,240,313,CK
under_voltage UNKNOWN

Certifications

emc ['IEC 62920', 'interference emission class B', 'ETSI EN 300 328 / ETSI EN 301 489 (radio, listed in the downloads section)']
grid_codes ['IEC 62116', 'IEC 61727', 'IEC 62909', 'EN 50549-1 (RfG)', 'AS/NZS 4777.2', 'CEI 0-21', 'ABNT NBR 16149', 'ABNT NBR 16150']
other ['LCA Review Report Fronius GEN24 Plus', 'TUEV factory inspection 2025']
regional ['UNKNOWN']
safety ['IEC 62109', 'IEC 62109-1', 'IEC 62109-2', 'IEC 62477-1', 'IEC 62368-1']

Warranty & service

conditions UNKNOWN
cycle_life UNKNOWN
design_life_years UNKNOWN
extended_options_years UNKNOWN
fan_replaceable yes (INFERRED, see field_replaceable_parts)
field_replaceable_parts ['fan (INFERRED from the Fan test function description in the operating instructions)']
fuse_replaceable UNKNOWN
service_intervals UNKNOWN
standard_years UNKNOWN

Packaging & logistics

gross_weight_kg 19
package_depth_mm UNKNOWN
package_height_mm UNKNOWN
package_width_mm UNKNOWN
transport_restrictions UNKNOWN
units_per_pallet UNKNOWN

Documents

certificate {# Located but never retrieved: listed, but deliberately not linked, and it backs no stored value. #} Fronius Primo GEN24 certificates portal — located, not retrieved rev UNKNOWN
datasheet Fronius Primo GEN24 5.0 Plus - Technical Data (HTML) rev UNKNOWN (live HTML page)
installation-manual Fronius Primo GEN24 3 - 6 kW / 3 - 6 kW Plus / 3 - 6 kW SC / 3 - 6 kW SC Plus Operating instructions (HTML) rev 043-01092026
quick-start Quick Start Guide Fronius Primo GEN24 3.0 - 10.0 kW rev 42,0410,2367 035-29042024
user-manual Fronius Smart Meter TS 65A-3 Operating Instructions rev 42,0426,0349,EN 006-05082020

Documented compatibility

Documented pairings only. A product absent here has no fetched document naming the pairing — that is not a statement that it fails.

inverter_battery

BYD Battery-Box Premium HVS 12.8 COMPATIBLEofficially-verified
https://www.fronius.com/en-gb/uk/solar-energy/installers-partners/technical-data/all-products/inverters/fronius-primo-gen24-plus/fronius-primo-gen24-5-0-plus (fetched 2026-09-01)
BYD Battery-Box Premium HVS 5.1 COMPATIBLEmanufacturer-documented
BYD Battery-Box Premium HVS&HVM Compatible Inverter List V2.21 (2025-08-20)
BYD Battery-Box Premium HVM 11.0 COMPATIBLEmanufacturer-documented
BYD Battery-Box Premium HVS&HVM Compatible Inverter List V2.21 (2025-08-20)

inverter_meter

Fronius Smart Meter TS 65A-3 COMPATIBLEmanufacturer-documented
Fronius Smart Meter TS 65A-3 Operating Instructions 42,0426,0349,EN 006-05082020, https://www.europe-solarstore.com/download/fronius/monitoring-and-control/Fronius_Smart_Meter_TS_65A-3_operating_instructions.pdf (fetched 2026-09-01); corroborated by the RS485 interface row on https://www.fronius.com/en-gb/uk/solar-energy/installers-partners/technical-data/all-products/inverters/fronius-primo-gen24-plus/fronius-primo-gen24-5-0-plus ('2x RS485 - Modbus RTU SunSpec (third-party supplier) / Fronius Smart Meter,

Recorded conflicts

max_short_circuit_current_per_mppt_a Review required
41.25 / 22 A — Fronius UK technical-data page, 'Max. short circuit current, module array*', with footnote 'Isc pv = Isc max >= Isc (STC) x 1,25'
33 / 18 A — Fronius Quick Start Guide 42,0410,2367 035-29042024, 'Max. short-circuit current (ISC PV = ISC max) 33 A (MPPT1) / 18 A (MPPT2)' for Primo GEN24 3-6 kW
The two documents apply the IEC 60364-7-712 / AS-NZS 5033 1.25 design factor differently: 33 x 1.25 = 41.25 exactly, so the technical-data page publishes the already-multiplied design value while the quick start guide publishes the array Isc. Use 33/18 A as the module-array Isc(STC) limit and 41.25/22 A as the Isc-max design figure.
max_short_circuit_current_per_mppt_a Review required
41.25 / 22 A — Fronius UK technical-data page, 'Max. short circuit current, module array*', with footnote 'Isc pv = Isc max >= Isc (STC) x 1,25'
33 / 18 A — Fronius Quick Start Guide 42,0410,2367 035-29042024, 'Max. short-circuit current (ISC PV = ISC max) 33 A (MPPT1) / 18 A (MPPT2)' for Primo GEN24 3-6 kW
The two documents apply the IEC 60364-7-712 / AS-NZS 5033 1.25 design factor differently: 33 x 1.25 = 41.25 exactly, so the technical-data page publishes the already-multiplied design value while the quick start guide publishes the array Isc. Use 33/18 A as the module-array Isc(STC) limit and 41.25/22 A as the Isc-max design figure.

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

AC voltage range (Umin - Umax)155 - 270 V
Back-up power1~NPE 220 V / 230 V; nom. output current 22,7 A (220 VAC) / 21,7 A (230 VAC)
Dynamic Peak Manager mode 'On (MLSD)'Optimized for systems with Module Level Shutdown devices (MLSD); not suitable for PV optimizers
European efficiency (etaEU)96.3 / 97.2 / 96.7 (230Vdc / 400Vdc / 530Vdc)
Frequency in backup power mode53 Hz
Grid connection (Uac,r)1~ NPE 220/230 V
Interference emission classB
Inverter designTransformerless
Leakage current factor to reduce RCMU/FI false tripping0 - 0.25 (default 0.16)
MPP adaptation efficiency99.9
Max. AC output current27,5 A
Max. efficiency (PV - grid)97,6 %
Max. switchover time PV-Point / Full Backup15 s / 10 s
Night-time consumption< 10 W
Nominal input voltage (Udc,r)400 V
Number of DC connections2+2
Output Data PV Point - Max continuous output power3000 VA
RCD recommendationFronius recommends a residual current circuit breaker suitable for frequency inverters with a release current of at least 100 mA
Usable MPP voltage range65 - 530 V