⚡ANMASystem BuildingAutomation, Network, Monitoring & Analytics
★PREMIUM

Knowledge Base › Inverters

Qcells Q.VOLT HYB-G3 10.0 kW 3P

Official manufacturer EU verified Sept. 22, 2026

Unresolved safety-relevant conflict
Two sources give different figures for a value on this product and nobody has resolved it. The specifications below are shown as recorded, but this product must not be treated as verified for engineering purposes until the conflict is closed.

Identity

brand Qcells
category inverters
ean —
firmware {'documented_version': 'UNKNOWN', 'constraints': 'UNKNOWN'}
generation G3
manufacturer Qcells
manufacturer_key qcells
market_version EU (VDE 4105 / EN 50549-1 / CEI 0-21 / TOR Erzeuger Typ A / PPDS)
model Q.VOLT HYB-G3 10.0 kW 3P
model_key qvolthybg3100kw3p
mpn —
product_family Q.VOLT
product_status active
region EU
release_year —
series Q.VOLT HYB-G3
sku —
variant 3P

Electrical

ac_connection 3P / N / PE
ac_voltage_range —
battery_capacity_range_kwh —
battery_communication —
battery_max_charge_current_a —
battery_max_charge_power_w —
battery_max_discharge_current_a —
battery_max_discharge_power_w —
battery_nominal_battery_voltage_v —
battery_supported True
Q.HOME+ ESS HYB-G3-3P Energy Storage Solution
battery_type —
battery_voltage_max_v 480
Q.HOME+ ESS HYB-G3-3P Energy Storage Solution
battery_voltage_min_v 80
Q.HOME+ ESS HYB-G3-3P Energy Storage Solution
battery_voltage_range_v —
eps_peak_power 15.0 kVA for 60 s
eps_phase 3P
eps_rated_power_va 10000.0
eps_switchover_time_ms < 100
eps_voltage 400
european_efficiency_pct 97.0
external_transfer_switch_required —
frequency_range_hz —
inrush_current —
max_ac_active_power_w —
max_ac_current_a 16.1
max_ac_power_va 11000
Q.HOME+ ESS HYB-G3-3P Energy Storage Solution
max_apparent_power_va 11000.0
max_backfeed_current_a —
max_charge_current_a 30
Q.HOME+ ESS HYB-G3-3P Energy Storage Solution
max_dc_input_power_w 15000.0
max_dc_voltage_v 1000 (nominal operating voltage 630)
max_discharge_current_a 30
Q.HOME+ ESS HYB-G3-3P Energy Storage Solution
max_efficiency_pct 97.6
max_input_current_per_mppt_a 28 (input A) / 16 (input B) disputed
max_output_fault_current_a 68 (at 5 ms, all types 5 - 15 kW)
max_pv_input_voltage_v 1000
Q.HOME+ ESS HYB-G3-3P Energy Storage Solution
max_short_circuit_current_per_mppt_a 35 (input A) / 20 (input B) disputed
mppt_efficiency_pct 99.9
mppt_topology_notation "2 / A:2, B:1 as printed"
mppt_voltage_max_v 950
Q.HOME+ ESS HYB-G3-3P Energy Storage Solution
mppt_voltage_min_v 180
Q.HOME+ ESS HYB-G3-3P Energy Storage Solution
mppt_voltage_range_v 180 - 950
night_self_consumption_w —
nominal_ac_voltage 380 / 400 / 415, 3P / N / PE
nominal_dc_voltage_v —
nominal_frequency_hz 50 / 60
nominal_grid_voltage_v 380 / 400 / 415 (3P/N/PE)
Q.HOME+ ESS HYB-G3-3P Energy Storage Solution
number_of_mppt 2
Q.HOME+ ESS HYB-G3-3P Energy Storage Solution
number_of_pv_inputs 3
Q.HOME+ ESS HYB-G3-3P Energy Storage Solution
official_manual_url https://cdn.webshopapp.com/shops/264724/files/380529495/q-cells-installationsanleitung-benutzerhandbuch-qv.pdf
Qcells Installationsanleitung- und Benutzerhandbuch Q.VOLT HYB-G3-3P (6.0/8.0/10.0/12.0/15.0 kW)
parallel_capability D variant has an integrated DC switch for parallel installation
phase_count 3
Q.HOME+ ESS HYB-G3-3P Energy Storage Solution
power_factor_range 0.8 leading ~ 0.8 lagging
rated_ac_power_va 10000
Q.HOME+ ESS HYB-G3-3P Energy Storage Solution
rated_ac_power_w 10000.0
rated_mppt_voltage_range_v —
startup_voltage_v 200
strings_per_mppt A:2, B:1
strings_per_mppt_distribution [2, 1]
Q.HOME+ ESS HYB-G3-3P Energy Storage Solution
thd_pct < 3 (THDi, rated power)

Physical / mechanical

ac_terminal —
cooling Natural convection / Forced convection
dc_connector —
depth_mm 199
dimensions_mm 503 x 503 x 199
display LCD, backlight, 20 x 4 character
enclosure_material —
height_mm 503
mounting —
noise_db < 35
weight_kg 30
width_mm 503

Installation

cable_requirements —
commissioning —
installation_angle —
mounting_clearances —
torque —

Environment

ingress_protection IP65
max_altitude_m 3000
operating_temperature_c -35 - +60 (derating at +45)
pollution_degree —
protective_class Class I
relative_humidity_pct 0 - 100 (non-condensing)
storage_temperature_c -40 - +65

Interfaces & connectors

app —
communication ['E-Meter', 'WLAN', 'Ethernet', 'USB', 'Dry Contact', 'RS485', 'CAN 2.0']
dry_contact —
meter_interface E-Meter
monitoring_portal —
protocols []

Protection

anti_islanding Anti-islanding protection
arc_fault —
dc_switch Yes (D variant)
insulation_monitoring Array insulation detection
overvoltage_category III (AC) / II (DC)
rcmu Residual current detection
reverse_polarity —
surge_protection_ac Integrated SPD, AC (Type II)
surge_protection_dc Integrated SPD, DC (Type II)

Certifications

standards ['EN 62109-1', 'EN 62109-2', 'EN 61000-6-1 2007', 'EN 61000-6-2 2005', 'EN 61000-6-3', 'EN 61000-6-4', 'EN 61000-3-2', 'VDE 4105', 'EN 50549-1', 'CEI 0-21', 'TOR Erzeuger Typ A', 'PPDS']

Warranty & service

conditions —
extension_options —
standard_years 10

Documents

datasheet Q.HOME+ ESS HYB-G3-3P Energy Storage Solution rev Rev08
manual Qcells Installationsanleitung- und Benutzerhandbuch Q.VOLT HYB-G3-3P (6.0/8.0/10.0/12.0/15.0 kW)

Recorded conflicts

electrical.max_short_circuit_current_per_mppt_a Review required
35 (input A) / 20 (input B) — stored value
[35, 20] — Max. input current (short circuit current) (input A / input B) 28 (35) / 16 (20) (axis: input A, input B)
Detected during import v1-freeze-2026-09-batch09
electrical.max_input_current_per_mppt_a Review required
28 (input A) / 16 (input B) — stored value
[28, 16] — Max. input current (short circuit current) (input A / input B) 28 (35) / 16 (20) (axis: input A, input B)
Detected during import v1-freeze-2026-09-batch09
electrical.startup_voltage_v Resolved — accepted incoming value
200 (start operating voltage) — stored value
200 — MPP voltage range (start operating voltage) 180 - 950 (200)
Detected during import v1-freeze-2026-09-batch09

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

Battery charge / discharge efficiency [%]97.0 / 97.0
Max. apparent AC power (INPUT - AC) [kVA]20
Max. current (INPUT - AC) [A]32.0
Max. input current (short circuit current) (input A / input B) [A]28 (35) / 16 (20)
Max. input current (short circuit)16(20)/16(20) ... 28(35)/16(20)
No. of MPP trackers / strings per MPP tracker2 / A:1, B:1 ... 2 / A:2, B:1
battery.communicationUNKNOWN
battery.max_charge_current_aUNKNOWN
battery.max_charge_power_wUNKNOWN
battery.max_discharge_current_aUNKNOWN
battery.max_discharge_power_wUNKNOWN
battery.nominal_battery_voltage_vUNKNOWN
identity.variant_as_researched3P; -D variant with integrated DC switch for parallel installation is offered but has no separate specification column
withheld:pv.mppt_topology_notation"2 / A:2, B:1 as printed"