ANMASystem BuildingAutomation, Network, Monitoring & Analytics
PREMIUM

Knowledge BaseInverters

SolaX Power X1-BOOST-5K-G4

Official manufacturer global verified Sept. 1, 2026

Identity

brand SolaX
category inverters
ean UNKNOWN
generation G4
manufacturer SolaX Power
market_version UNKNOWN
model X1-BOOST-5K-G4
mpn X1-BOOST-5K-G4
product_family X1-BOOST G4 Series 2.5-6 kW single-phase grid-tie
product_revision UNKNOWN
product_status active
region global
release_year UNKNOWN
sku UNKNOWN

Electrical

ac_coupling_support UNKNOWN
api_cloud UNKNOWN
api_local UNKNOWN
backup_eps_output_support False
battery_support False
battery_type N/A
battery_voltage_class N/A
battery_voltage_max_v N/A
battery_voltage_min_v N/A
communication_can UNKNOWN
communication_ethernet UNKNOWN
communication_rs232 UNKNOWN
communication_rs485 True
communication_wifi UNKNOWN (Pocket dongle ecosystem expected; not stated in fetched rows)
ct_support optional CT
generator_input_support N/A
grid_certifications ['IEC/EN 62109-1/-2', 'EN61000-6-1/2/3/4']
grid_export_control true ('Export control function in-built'; optional Meter/CT)
grid_frequency_hz 50 / 60
grid_voltage_v 1 / N / PE, 220 / 230 / 240
home_assistant_integration UNKNOWN
max_ac_power_kw 5
max_battery_charge_current_a N/A
max_battery_charge_power_kw N/A
max_battery_discharge_current_a N/A
max_dc_voltage_v 600
max_input_current_per_mppt_a 16
max_parallel_units UNKNOWN
max_pv_input_power_w 10000
max_short_circuit_current_per_mppt_a 22
modbus_rtu UNKNOWN
modbus_tcp UNKNOWN
mppt_max_voltage_v 600
mppt_min_voltage_v 35
num_mppt 2
officially_supported_battery_brands N/A
parallel_support UNKNOWN
phase_type single-phase
pv_inputs_per_mppt 1
pv_oversizing_ratio 2.0 (10.0 kWp recommended array on 5 kW AC)
rated_ac_power_kw 5
region_variant UNKNOWN
smart_meter_support optional Meter (model not named in datasheet)
sources [{'url': 'https://www.solaxpower.com/uploads/file/solax-x1-boost-g4-datasheet-en.pdf', 'title': 'X1-BOOST G4 Datasheet (EN)', 'doc_type': 'datasheet', 'publisher': 'SolaX Power', 'revision': 'V1.2', 'doc_date': 'UNKNOWN', 'language': 'en', 'accessed': '2026-09-01', 'confidence': 'officially-verified'}, {'url': 'https://www.sunecor.com/wp-content/uploads/2024/12/Solax-X1-BOOST-G4-datasheet-en.pdf', 'title': 'X1-BOOST G4 Datasheet (EN, newer revision V1.6.1, distributor-hosted mirror)', 'doc_type': 'datasheet-mirror', 'publisher': 'SolaX Power (hosted by Sunecor)', 'revision': 'V1.6.1', 'doc_date': '2024-12 (upload)', 'language': 'en', 'accessed': '2026-09-01', 'confidence': 'manufacturer-documented'}]
startup_voltage_v 50
sunspec_support UNKNOWN
topology grid-tie

Physical / mechanical

bracket_dimensions_mm UNKNOWN
cable_entry_positions bottom of the unit
cable_gland_sizes UNKNOWN
depth_mm 146
enclosure_material UNKNOWN
height_mm 274
housing_color UNKNOWN
mounting_bolt_size expansion bolt + self-tapping screw (supplied)
mounting_hole_diameter_mm 10
mounting_hole_spacing_mm 223 (bracket drawing, installation manual pp.5-6)
X1-BOOST G4 + Pocket WiFi V3.0 (16A) Installation Manual (EN) — installation manual pp.5-6 bracket drawing, 223 mm
mounting_plate_dimensions_mm UNKNOWN
mounting_type ['wall']
screw_sizes UNKNOWN
shipping_weight_kg UNKNOWN
terminal_locations 2x PV positive/negative connectors, AC connector, COM/CT port, USB, RS485, DRM, heat-pump port, DC switch
torque_specs 1.2 +/- 0.1 N.m for the bracket mounting (installation manual p.8)
X1-BOOST G4 + Pocket WiFi V3.0 (16A) Installation Manual (EN) — installation manual p.8: '1.2 +/- 0.1 N.m'
weight_kg 11 (datasheet V1.2); 11.5 (installation manual p.19) - see data_conflicts
width_mm 404
X1-BOOST G4 Datasheet (EN) — datasheet row 'Dimensions (WxHxD) 404x274x146'; installation manual p.19 identical

Installation

altitude_derating_note UNKNOWN
clearance_between_units_mm 350
clearance_bottom_mm 300
clearance_front_mm UNKNOWN
clearance_left_mm 300
clearance_right_mm 300
clearance_top_mm 300
cooling_airflow_requirements natural cooling
direct_sunlight_restriction avoid direct sunlight, rain exposure and snow lay up (installation manual p.4)
drill_hole_depth_mm 60
X1-BOOST G4 + Pocket WiFi V3.0 (16A) Installation Manual (EN) — installation manual pp.5-6: 'diameter-10 mm', 'Depth: >=60 mm'
drill_hole_diameter_mm 10
indoor_outdoor indoor or outdoor (IP66)
installation_humidity_range UNKNOWN
installation_temperature_range_c UNKNOWN
max_installation_altitude_m 4000
minimum_wall_thickness_mm UNKNOWN
mounting_orientation wall mount; installation angle <= 5 degrees
orientation_allowed ['vertical wall (tilt <= 5 degrees)']
orientation_forbidden UNKNOWN (the installation manual states only 'Installation Angle <=5 degrees')
surface_requirements the carrier must be fire resistant and suitable for the device dimensions and weight (installation manual p.5)
two_person_lift_required UNKNOWN
ventilation_requirements UNKNOWN

Environment

cooling_method natural cooling ('Nature cooling')
corrosion_class UNKNOWN
fan_replaceable N/A (fanless)
ik_rating UNKNOWN
ip_rating IP66
X1-BOOST G4 Datasheet (EN) — datasheet row 'IP rating IP66'
max_altitude_m 4000
nema_rating UNKNOWN
noise_level_db 25 dB
X1-BOOST G4 Datasheet (EN) — datasheet row 'Noise emission 25'
operating_temperature_c -25 ~ 60
pollution_degree UNKNOWN
relative_humidity 0 ~ 100 %
salt_mist_resistance UNKNOWN
storage_temperature_c -30 ~ 70
uv_resistance UNKNOWN

Interfaces & connectors

ac_terminal_type supplied AC connector; 3-core copper 4~6 mm2 for the 5K model
bluetooth UNKNOWN
can UNKNOWN
cellular optional Pocket 4G dongle
drm yes
ethernet optional Pocket LAN dongle
heat_pump_port yes (heat-pump port on the COM/CT connector, installation manual pp.10-11)
modbus_rtu UNKNOWN
modbus_tcp UNKNOWN
protocol_notes Datasheet communication row verbatim: 'USB/RS485/DRM, Optional: Meter/CT'; optional monitoring dongle 'Pocket WiFi/LAN/4G'
pv_connector_type 2x supplied PV positive/negative connectors with pin contacts; brand not named
rs485 yes
sunspec UNKNOWN
usb yes
wifi optional Pocket WiFi dongle

Controls & display

audible_alarm UNKNOWN
buttons Up/ESC button and Down/Enter button
display_type 2 x LED + LCD (16 x 2) / APP
leds operating indicator light (blue normal / flashing); error indicator light (red fault)
local_display True
mobile_app yes (datasheet display row lists 'APP')
remote_display_option UNKNOWN
status_indicators UNKNOWN
touchscreen False
web_interface UNKNOWN

Protection

ac_auxiliary_power_supply Optional (APS)
afci Optional
anti_islanding yes
back_feed_current_monitoring yes
dc_injection_monitoring yes
grid_monitoring yes
ground_fault_protection yes (monitoring ground fault protection)
insulation_monitoring yes (DC isolation protection)
integrated_breakers_fuses UNKNOWN
integrated_dc_switch True
over_current UNKNOWN
over_temperature yes
over_voltage yes (over/under voltage protection)
overvoltage_category UNKNOWN
protection_class UNKNOWN
residual_current_monitoring yes (residual current detection)
reverse_polarity UNKNOWN
short_circuit UNKNOWN
surge_protection SPD (DC/AC): Type II / Type II (Optional)
under_voltage yes

Certifications

emc ['EN61000-6-1', 'EN61000-6-2', 'EN61000-6-3', 'EN61000-6-4', 'EN61000-3-2', 'EN61000-3-3', 'EN61000-3-11', 'EN61000-3-12']
grid_codes ['IEC61727', 'EN50549', 'G98/G99', 'AS 4777.2', 'VDE4105', 'CEI 0-21', 'VFR', 'PPDS', 'TOR']
X1-BOOST G4 Datasheet (EN) — datasheet 'Grid code certifications' row
other []
regional []
safety ['IEC / EN 62109-1', 'IEC / EN 62109-2']

Warranty & service

conditions UNKNOWN
cycle_life N/A
design_life_years UNKNOWN
extended_options_years UNKNOWN
fan_replaceable N/A (fanless)
field_replaceable_parts UNKNOWN
fuse_replaceable UNKNOWN
service_intervals UNKNOWN
standard_years UNKNOWN

Documents

datasheet X1-BOOST G4 Datasheet (EN) rev V1.2
datasheet {# Located but never retrieved: listed, but deliberately not linked, and it backs no stored value. #} X1-BOOST G4 Datasheet V1.6.1 (distributor-hosted mirror of the official document) — located, not retrieved rev V1.6.1
installation-manual X1-BOOST G4 + Pocket WiFi V3.0 (16A) Installation Manual (EN) rev UNKNOWN
product-page X1-BOOST G4 product page rev UNKNOWN

Recorded conflicts

mppt_voltage_range Review required
35~600 — V1.6.1 mirror datasheet (currently stored)
40~560 — official solaxpower.com datasheet V1.2, 'MPP tracker voltage range 40~560'
datasheet revision (previously logged conflict, re-confirmed against the official V1.2 document this session)
max_input_current_per_mppt_a Review required
16 — value currently stored on the record (V1.6.1 mirror, labelled row 'Max. input current per MPPT(MPPT1/2) 16 A / 16 A')
22 — official solaxpower.com datasheet V1.2, 'Max PV input current 22'
datasheet revision, or V1.2 printing the short-circuit current in the input-current row (V1.2's Isc row also reads 22)
max_pv_input_power_w Review required
10000 — value currently stored on the record (from the V1.6.1 mirror datasheet)
8000 — official solaxpower.com datasheet V1.2, 'Max PV array input power 8000'
datasheet revision - the V1.2 sheet states 8000 W while also giving 'DC oversizing 200%' (= 10000 W on a 5 kW AC unit), so the two figures are internally inconsistent within V1.2
max_input_current_per_mppt_a Resolved — imported outcome unspecified
16 — V1.6.1 mirror (verbatim labeled row)
22 — solaxpower.com V1.2 first-pass extraction
first-pass extraction likely assigned the 22 A short-circuit value to the input-current row
physical.weight_kg Review required
11 — official X1-BOOST G4 datasheet V1.2, 'Weight 11'
11.5 — official X1-BOOST G4 + Pocket WiFi installation manual p.19, 'Weight [kg] 11.5'
document revision, or the manual quoting the weight including the supplied accessories
mppt_voltage_range Review required
35~600 — V1.6.1 mirror datasheet (verbatim row)
40~560 — solaxpower.com V1.2 datasheet extraction
doc revision, or the V1.2 figure being a separate full-load MPPT-range row picked up by extraction
physical.weight_kg Review required
11 — official X1-BOOST G4 datasheet V1.2, 'Weight 11'
11.5 — official X1-BOOST G4 + Pocket WiFi installation manual p.19, 'Weight [kg] 11.5'
document revision, or the manual quoting the weight including the supplied accessories
max_pv_input_power_w Review required
10000 — value currently stored on the record (from the V1.6.1 mirror datasheet)
8000 — official solaxpower.com datasheet V1.2, 'Max PV array input power 8000'
datasheet revision - the V1.2 sheet states 8000 W while also giving 'DC oversizing 200%' (= 10000 W on a 5 kW AC unit), so the two figures are internally inconsistent within V1.2
max_input_current_per_mppt_a Resolved — imported outcome unspecified
16 — V1.6.1 mirror (verbatim labeled row)
22 — solaxpower.com V1.2 first-pass extraction
first-pass extraction likely assigned the 22 A short-circuit value to the input-current row
mppt_voltage_range Review required
35~600 — V1.6.1 mirror datasheet (verbatim row)
40~560 — solaxpower.com V1.2 datasheet extraction
doc revision, or the V1.2 figure being a separate full-load MPPT-range row picked up by extraction

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

AC voltage range / frequency range90~290 V; +/-5 Hz
DC oversizing200%
Multiple-inverter spacing>=35 cm between units
Nominal input voltage360 V
Standby consumption<3 W
conflict.status[max_input_current_per_mppt_a]resolved-in-favor-of-16