ANMASystem BuildingAutomation, Network, Monitoring & Analytics
PREMIUM

Knowledge BaseInverters

Sungrow SG10RS

Official manufacturer AU verified Sept. 3, 2026

Unresolved safety-relevant conflict
Two sources give different figures for a value on this product and nobody has resolved it. The specifications below are shown as recorded, but this product must not be treated as verified for engineering purposes until the conflict is closed.

Identity

brand Sungrow
category inverters
ean UNKNOWN
generation RS string inverter disputed
grid_type TN / TT
hardware_revision UNKNOWN
legacy_name UNKNOWN
manufacturer Sungrow
manufacturer_legal_entity Sungrow Power Supply Co., Ltd.
market_version AU (AS/NZS 4777.2:2020) disputed
model SG10RS
mpn UNKNOWN
order_code UNKNOWN
phase_configuration single-phase (1 / N / PE)
product_family SG5.0RS-ADA / SG8.0RS / SG9.0RS / SG10RS disputed
product_status active
product_status_detail not listed on the official 2026 sungrowpower.com string-inverter index (which shows only SG3.0/3.6/4.0RS and SG5.0/6.0RS for 1-phase on the global site); the family remains current in AU and LATAM. Status recorded as regionally-scoped rather than globally-active.
product_status_evidence official global product index fetched 2026-09-03
region AU
release_year UNKNOWN
sku UNKNOWN
subcategory grid-tied PV string inverter (single-phase, no battery interface)
topology transformerless (no galvanic isolation)
variant_note Family also includes SG5.0RS-ADA (AU arc-detection variant) and the Brazilian '-L' variants SG8.0RS-L / SG9.0RS-L / SG10RS-L, which are separate records and were not researched here. ENRICHMENT TARGET: ANMA already holds an SG10RS record built from the AU V14 datasheet. This record is the GLOBAL (GL V12) variant and is electrically different (see data_conflicts).

Electrical

ac_coupling_support UNKNOWN
backup_eps_output_support false (INFERRED: grid-tie string inverter, no backup output in datasheet)
battery_support False
battery_type None (grid-tie string inverter; no battery support in datasheet V14)
battery_voltage_class N/A (no battery interface)
battery_voltage_max_v N/A (no battery interface)
battery_voltage_min_v N/A (no battery interface)
communication_can UNKNOWN
communication_ethernet True
communication_rs485 True
communication_wifi True
ct_support UNKNOWN
dc_ac_ratio 1.5
european_efficiency_pct 97.4
feed_in_phases 1 / 1
generator_input_support N/A (grid-tie)
grid_certifications ['IEC 62109-1/2', 'AS/NZS 4777.2:2020']
grid_export_control UNKNOWN (DI for 'Ripple control & DRM' listed; export-limit meter not captured in fetched excerpt)
grid_frequency_hz 50/60
grid_frequency_range 45 Hz - 55 Hz (50 Hz) / 55 Hz - 65 Hz (60 Hz)
grid_voltage_v 220/230/240
SG5.0RS-ADA/SG8.0/10RS Datasheet — 'Rated grid voltage 220 V / 230 V / 240 V'; 'Grid voltage range 154 V - 276 V'
home_assistant_integration UNKNOWN
max_ac_power_kw 9.999 (label 'Max apparent power 9999 VA')
max_ac_power_w 10000
max_apparent_power_va 10000
max_battery_charge_current_a N/A (no battery interface)
max_battery_charge_power_kw N/A (no battery interface)
max_battery_discharge_current_a N/A (no battery interface)
max_dc_short_circuit_current_total_a 60
max_dc_voltage_v 600
max_efficiency_pct 97.8
max_input_current_per_input_a 16
max_input_current_per_mppt_a 20 (label 'Max. PV input current 60 A (20 A / 20 A / 20 A)') disputed
max_input_current_total_a 48
max_output_current_a 45.5
max_pv_input_power_w 12000 (label 'Recommended max. PV input power 12 kWp')
max_short_circuit_current_per_mppt_a 30 (fetched excerpt showed single figure 'Max DC short-circuit current 30 A'; per-MPPT vs total breakdown not captured) disputed
min_operating_voltage_v 40
modbus_rtu UNKNOWN
modbus_tcp UNKNOWN
mppt_max_voltage_v 560
mppt_min_voltage_v 40
mppt_voltage_max_v 560
mppt_voltage_min_v 40
mppt_voltage_range_for_nominal_power UNKNOWN
night_power_consumption UNKNOWN
nominal_dc_voltage_v 360
nominal_frequency 50 Hz / 60 Hz
nominal_voltage 220 V / 230 V / 240 V (1 / N / PE)
num_mppt 3
num_pv_inputs 3
officially_supported_battery_brands N/A (no battery support)
oversizing_guidance recommended max PV input power 15.0 kWp vs 10000 W rated AC (1.5x)
phase_type single-phase
power_factor_range > 0.99 default; 0.8 leading - 0.8 lagging
pv_inputs_per_mppt 1
rated_ac_power_kw 9.999 (label 'Rated output power 9999 W' - AU single-phase limit design)
rated_ac_power_w 10000
rated_output_current_a 43.5
recommended_pv_power_w 15000
region_variant AU (datasheet V14 EN(AU); 'SG5.0RS-ADA' sibling is the arc-detection AU 5 kW variant)
smart_meter_support UNKNOWN
sources [{'url': 'https://info-support.sungrowpower.com/application/pdf/2024/12/07/DS_20241204_SG5.0RS-ADA_8.0_10RS_Datasheet_V14_EN%EF%BC%88AU).pdf', 'title': 'SG5.0RS-ADA/SG8.0/10RS datasheet', 'doc_type': 'datasheet', 'publisher': 'Sungrow', 'revision': 'Version 14', 'doc_date': '2024-12-04', 'language': 'en', 'region': 'AU', 'accessed': '2026-09-01', 'confidence': 'officially-verified'}]
startup_voltage_v 50
string_rules 3 independent MPPTs, 1 PV string per MPPT (3 strings total)
sunspec_support UNKNOWN
thd < 3 % at rated power
topology grid-tie (transformerless string inverter, no battery interface)
voltage_range 154 V - 276 V

Physical / mechanical

cooling natural convection (fanless)
depth_mm 170
dimensions_mm 490 (W) * 340 (H) * 170 (D)
enclosure_material UNKNOWN
height_mm 340
mounting_bolt_size UNKNOWN
mounting_hole_diameter_mm UNKNOWN
mounting_hole_spacing_mm UNKNOWN
mounting_type ['wall'] disputed
screw_sizes UNKNOWN
shipping_weight_kg UNKNOWN
torque_specs UNKNOWN
weight_kg 19
SG5.0RS-ADA/SG8.0/10RS Datasheet — 'Weight 19 kg', SG10RS column
width_mm 490
SG5.0RS-ADA/SG8.0/10RS Datasheet — 'Dimensions (W*H*D) 490 * 340 * 170 mm', SG10RS column

Installation

ac_connector plug-and-play connector (max. 16 mm2)
dc_connector MC4 (max. 6 mm2)
direct_sunlight_restriction UNKNOWN
indoor_outdoor indoor and outdoor (IP65)
max_installation_altitude_m 4000
mounting_orientation UNKNOWN (no official SG-RS installation manual could be retrieved this session)

Environment

cooling natural cooling
cooling_method natural cooling
corrosion_class C5 disputed
SG5.0RS-ADA/SG8.0/10RS Datasheet — 'Anti-corrosion class C5'
fan_replaceable N/A (fanless)
ip_rating IP65
max_altitude_m 4000
noise_db UNKNOWN
noise_level_db UNKNOWN
operating_temperature -25 C to 60 C
operating_temperature_c -25 to 60
relative_humidity 0 % - 100 %

Interfaces & connectors

ac_terminal_type plug-and-play connector (max. 16 mm2)
bluetooth UNKNOWN
can none documented
communication_label Ethernet / WLAN / RS485 / DI (Ripple control & DRM)
digital_inputs DI for ripple control and DRM
display LED digital display and LED indicator
ethernet yes
isolarcloud_dependency iSolarCloud for monitoring; no local-operation dependency stated
local_communication RS485 / DI (ripple control and DRM)
logger_support NOT_LISTED for SGxxRS in Compatibility List 4.3
modbus_rtu UNKNOWN
modbus_tcp UNKNOWN
protocol_notes Datasheet V14 'Communication: Ethernet / WLAN / RS485 / DI (Ripple control & DRM)'
pv_connector_type MC4 (max. 6 mm2)
register_map_availability UNKNOWN
rs485 yes
wifi yes (WLAN)
winet_support yes - Compatibility List 4.3 lists WiNet-S/S2 for SGxxRS

Controls & display

display_type LED digital display & LED indicator
leds LED indicator
local_display True
mobile_app iSolarCloud
touchscreen False

Protection

afci yes (integrated arc fault circuit interrupter) disputed
SG5.0RS-ADA/SG8.0/10RS Datasheet — protection section 'AFCI: Yes'; product page bullet 'Integrated arc fault circuit interrupter'
anti_islanding yes (grid monitoring / islanding protection) disputed
dc_reverse_polarity yes
dc_switch yes
grid_protection grid monitoring
ground_fault_protection yes (ground fault monitoring)
insulation_monitoring PV string current monitoring yes
integrated_dc_switch True
pid PID Zero function yes
rcmu leakage current protection yes
residual_current_monitoring yes (leakage current protection)
reverse_polarity yes (DC reverse polarity protection)
short_circuit yes (AC short-circuit protection)
spd DC Type II / AC Type II
surge_protection DC Type II / AC Type II (built-in)

Certifications

emc []
grid_codes ['AS/NZS 4777.2:2020'] disputed
grid_support active and reactive power control, power ramp rate control
other []
regional []
safety ['IEC 62109-1', 'IEC 62109-2']

Warranty & service

extension_options UNKNOWN
note no warranty statement appears in the fetched datasheet extraction
standard_warranty UNKNOWN

Documents

compatibility-list Sungrow Compatibility List Public 2026 (Version 4.3) rev 4.3
datasheet SG5.0RS-ADA/SG8.0/10RS Datasheet rev V14
datasheet SG8.0/9.0/10RS Datasheet V12 EN (GL) rev Version 12
product-page SG8.0/9.0/10RS product page rev live page
product-page Sungrow string inverter product index (official website) rev UNKNOWN
quick-start SG5.0RS-ADA / SG8.0RS / SG9.0RS / SG10RS Commissioning Guide rev UEN-Ver11-202310
user-manual {# Located but never retrieved: listed, but deliberately not linked, and it backs no stored value. #} SG5.0RS-ADA / SG8.0RS / SG9.0RS / SG10RS User Manual (Ver15) — located, not retrieved rev Ver15

Recorded conflicts

electrical.max_dc_short_circuit_current_total_a Review required
60 A total ('60 A (20 A / 20 A / 20 A)') — document[0]
30 A (single figure captured, per-MPPT breakdown not captured) — document[3]
electrical.max_input_current_per_mppt_a Review required
16 A per MPPT, 48 A total ('48 A (16 A / 16 A / 16 A)') — document[0]
20 A per MPPT, 60 A total ('60 A (20 A / 20 A / 20 A)') — document[3]
electrical.recommended_pv_power_w Review required
15000 W (15 kWp) — document[0]
12000 W (12 kWp) — document[3]
electrical.rated_ac_power_w / max_apparent_power_va Review required
10000 W / 10000 VA — document[0]
9999 W / 9999 VA — document[3]
electrical.max_short_circuit_current_per_mppt_a Review required
30 (fetched excerpt showed single figure 'Max DC short-circuit current 30 A'; per-MPPT vs total breakdown not captured) — stored value
20 — incoming package
Detected during import sungrow-full-portfolio-2026-09-03
electrical.max_input_current_per_mppt_a Review required
20 (label 'Max. PV input current 60 A (20 A / 20 A / 20 A)') — stored value
16 — incoming package
Detected during import sungrow-full-portfolio-2026-09-03
certifications.grid_codes Review required
['AS/NZS 4777.2:2020'] — stored value
['IEC/EN 62109-1/2', 'IEC/EN 62116', 'IEC/EN 61727', 'IEC/EN 61000-6-2/3', 'AS/NZS 4777.2', 'ABNT NBR 16149', 'ABNT NBR 16150', 'G99'] — incoming package
Detected during import sungrow-full-portfolio-2026-09-03
protection.anti_islanding Review required
yes (grid monitoring / islanding protection) — stored value
yes — incoming package
Detected during import sungrow-full-portfolio-2026-09-03
protection.afci Review required
yes (integrated arc fault circuit interrupter) — stored value
yes — incoming package
Detected during import sungrow-full-portfolio-2026-09-03
environment.corrosion_class Review required
C5 — stored value
C5 (per the AU V14 sibling; not surfaced in the GL V12 extraction) — incoming package
Detected during import sungrow-full-portfolio-2026-09-03
physical.mounting_type Review required
['wall'] — stored value
['wall bracket'] — incoming package
Detected during import sungrow-full-portfolio-2026-09-03
identity.generation Review required
RS string inverter — stored value
RS high-power (3-MPPT chassis, 490*340*170 mm) — incoming package
Detected during import sungrow-full-portfolio-2026-09-03
identity.market_version Review required
AU (AS/NZS 4777.2:2020) — stored value
GL (global) — incoming package
Detected during import sungrow-full-portfolio-2026-09-03
identity.product_family Review required
SG5.0RS-ADA / SG8.0RS / SG9.0RS / SG10RS — stored value
SG5.0RS-ADA / SG8.0RS / SG9.0RS / SG10RS (RS single-phase high-power, 3 MPPT) — incoming package
Detected during import sungrow-full-portfolio-2026-09-03

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

Matching meter (SG5.0RS-ADA)SG5.0RS-ADA matching single-phase wireless meter WiMeter-S
Max. efficiency / European efficiency97.8 % / 97.4 %
PID recovery functionYes
Power factor> 0.99 / 0.8 leading - 0.8 lagging
THD< 3 % (at rated power)
identity.product_statusnot listed on the official 2026 sungrowpower.com string-inverter index (which shows only SG3.0/3.6/4.0RS and SG5.0/6.0RS for 1-phase on the global site); the family remains current in AU and LATAM. Status recorded as regionally-scoped rather than globally-active.
identity.region_as_researchedGL (global datasheet V12); a separate AU datasheet V14 exists for AS/NZS 4777.2 markets
manufacturer_legal_entity_as_printedSungrow Power Supply Co., Ltd.

Build a system with this product