ANMASystem BuildingAutomation, Network, Monitoring & Analytics
PREMIUM

Knowledge BaseInverters

Sungrow SG10RT

Official manufacturer EU / GL verified Sept. 3, 2026

Unresolved safety-relevant conflict
Two sources give different figures for a value on this product and nobody has resolved it. The specifications below are shown as recorded, but this product must not be treated as verified for engineering purposes until the conflict is closed.

Identity

category inverters
ean UNKNOWN
generation RT 1st generation (superseded by the RT-P2 generation)
grid_type TN / TT
hardware_revision UNKNOWN
legacy_name UNKNOWN
manufacturer Sungrow
manufacturer_legal_entity Sungrow Power Supply Co., Ltd.
market_version UNKNOWN
model SG10RT
mpn UNKNOWN
order_code UNKNOWN
phase_configuration three-phase (3 / N / PE)
product_family SG5.0-12RT (RT three-phase residential/small-commercial string inverter, 1st generation)
product_status superseded
product_status_detail superseded - the official 2026 sungrowpower.com string-inverter index lists only 'SG5/6/7/8/10/12RT-P2' and 'SG15/17/20RT-P2'; the non-P2 RT models are no longer listed
product_status_evidence official product index fetched 2026-09-03
region EU / GL
release_year UNKNOWN
sku UNKNOWN
subcategory grid-tied PV string inverter (three-phase, no battery interface)
topology transformerless (no galvanic isolation)
variant_note SG10RT (non-P2) must not be collapsed with SG10RT-P2: the P2 generation has a different DC-current rating, different European efficiency and a different AC voltage range (175-276 V vs 180-276 V).

Electrical

dc_ac_ratio 1.5
european_efficiency_pct 97.9
feed_in_phases 3 / 3-PE
grid_frequency_range 45 Hz - 55 Hz / 55 Hz - 65 Hz
max_ac_power_w 11000
max_apparent_power_va 11000
max_dc_short_circuit_current_total_a UNKNOWN - see verification_notes (row-offset defect)
max_dc_voltage_note datasheet footnote: the inverter enters standby between 1000 V and 1100 V input; MC4 Evo2 connectors are required if the system exceeds 1000 V DC
max_dc_voltage_v 1100
max_efficiency_pct 98.5
max_input_current_per_input_a UNKNOWN
max_input_current_per_mppt_a 25 / 12.5 (MPPT1 / MPPT2 - asymmetric)
max_input_current_total_a 37.5
max_output_current_a 16.7
max_pv_input_power_w UNKNOWN
max_short_circuit_current_per_mppt_a UNKNOWN - see verification_notes (row-offset defect)
min_operating_voltage_v 180
mppt_voltage_max_v 1000
mppt_voltage_min_v 160
mppt_voltage_range_for_nominal_power UNKNOWN
night_power_consumption < 6 W
nominal_dc_voltage_v 600
nominal_frequency 50 Hz / 60 Hz
nominal_voltage 3 / N / PE, 220/380 V; 230/400 V; 240/415 V
num_mppt 2
num_pv_inputs 3 (2 strings on MPPT1, 1 on MPPT2 - implied by the asymmetric current split)
oversizing_guidance recommended max PV input power 15.0 kWp vs 10000 W rated AC (1.5x)
power_factor_range > 0.99 default; 0.8 leading - 0.8 lagging
rated_ac_power_w 10000
rated_output_current_a 14.5 A at 230 V
recommended_pv_power_w 15000
regional_derate Germany: max. AC output limited to 10000 VA (datasheet footnote)
startup_voltage_v 180
string_rules UNKNOWN - the 'No. of PV strings per MPP input' row is offset-affected in both fetched copies
thd < 3 % at rated power
voltage_range 180 V - 276 V (phase) / 311 V - 478 V (line)

Physical / mechanical

cooling natural cooling (fanless)
depth_mm 195
dimensions_mm 370 (W) * 480 (H) * 195 (D)
enclosure_material UNKNOWN
height_mm 480
mounting_type ['wall-mounting bracket']
weight_kg 18
width_mm 370

Installation

ac_connector plug and play
dc_connector MC4 (max. 6 mm2)
indoor_outdoor indoor and outdoor (IP65)
max_installation_altitude_m 4000
mounting_orientation UNKNOWN

Environment

cooling natural cooling
corrosion_class C5
ip_rating IP65
max_altitude_m 4000
night_power_consumption < 6 W
noise_db UNKNOWN
operating_temperature -25 C to 60 C
relative_humidity 0 % - 100 % non-condensing

Interfaces & connectors

bluetooth UNKNOWN
can none documented
communication_label WLAN / Ethernet / RS485 / DI / DO
display LED
ethernet yes
isolarcloud_dependency iSolarCloud for monitoring / remote updates; no local-operation dependency stated
local_communication RS485 / DI / DO
logger_support NOT_LISTED for SGxxRT in Compatibility List 4.3
modbus_rtu UNKNOWN
modbus_tcp UNKNOWN
register_map_availability UNKNOWN
rs485 yes
wifi yes (WLAN)
winet_support yes - Compatibility List 4.3 lists WiNet-S/S2 for SGxxRT

Protection

afci yes
anti_islanding yes
dc_reverse_polarity yes
dc_switch yes
grid_protection grid monitoring; LVRT, HVRT, active and reactive power control, power ramp rate control
insulation_monitoring ground fault monitoring; PV string current monitoring
pid PID recovery function yes
rcmu leakage current protection yes
spd DC Type II / AC Type II

Certifications

grid_codes IEC, EN, VDE, AS/NZS and other international standards (the V17 extraction returned the compliance list only at standards-body granularity)
safety UNKNOWN

Warranty & service

extension_options UNKNOWN
note no warranty statement appears in the fetched datasheet extraction
standard_warranty UNKNOWN

Documents

compatibility-list Sungrow Compatibility List Public 2026 (Version 4.3) rev 4.3
datasheet SG5.0/6.0/7.0/8.0/10/12RT Datasheet V1.1.3 (Sungrow document mirrored by Phaos) rev V1.1.3
datasheet SG5.0/6.0/7.0/8.0/10/12RT Datasheet V17 EN rev Version 17
directory-listing ENF Solar inverter directory entry for Sungrow SG5/6/7/8/10/12RT rev UNKNOWN
product-page Sungrow string inverter product index (official website) rev UNKNOWN
user-manual {# Located but never retrieved: listed, but deliberately not linked, and it backs no stored value. #} SG5.0-20RT User Manual (Ver13) — located, not retrieved rev Ver13

Recorded conflicts

electrical.max_short_circuit_current_per_mppt_a Review required
V17 extraction returned '5000 W / 6000 W / 8000 W / 10000 W / 12000 W' on this label - wattages, i.e. a foreign row — document[0]
Phaos V1.1.3 extraction returned only the parenthetical fragments '(12.5/12.5) A, (16/16) A, (25/12.5) A, (32/16) A' on this label — document[1]

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

identity.product_statussuperseded - the official 2026 sungrowpower.com string-inverter index lists only 'SG5/6/7/8/10/12RT-P2' and 'SG15/17/20RT-P2'; the non-P2 RT models are no longer listed
manufacturer_legal_entity_as_printedSungrow Power Supply Co., Ltd.

Build a system with this product