ABB (E-mobility; NA distribution via InCharge Energy) M4M 30
Official manufacturer GLOBAL verified Sept. 25, 2026
Identity
| category | smart_meters |
| manufacturer | ABB disputed |
| model | M4M 30 |
| product_status | active |
| region | GLOBAL |
| variant | Modbus RTU |
Electrical
| accuracy_class | Class 1 (IEC 62053-21) / Class B (EN 50470-3) |
| accuracy_class_active_energy |
Class 0,5 acc. to IEC 61557-12:2021
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
|
| auxiliary_supply_v |
48 to 240 VAC/VDC ±15%
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
|
| bidirectional | True |
| bidirectional_metering | True |
| ct_secondary_current_a |
[1, 5]
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
|
| direct_current_max_a |
not applicable - CT-connected
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
|
| grid_frequency_hz |
50-60
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
|
| local_modbus_available |
True
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
|
| max_current_a | 65.0 |
| measurement_directions |
Four-quadrant - import/export active, reactive and apparent energy
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
|
| measurement_type | Current Transformer (CT) |
| meter_type |
Front-panel network analyzer, CT-connected (4 current inputs L1, L2, L3, N)
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
|
| mid_approved |
False
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
|
| modbus_max_bus_length_m |
700
MODBUS MANUAL - M4M Network analyzers v.1.05
|
| modbus_max_slaves |
247
MODBUS MANUAL - M4M Network analyzers v.1.05
|
| official_manual_url |
https://library.e.abb.com/public/96e22792897740c3b79b2d758e9667df/2CSG445042D0201_en_M_User%20Manual%20M4M%2030-32.pdf?x-sign=2HBRZEyd492erLmaNYnfoxNzNlcBc8as7MbtkZJHqMbok2Gz5i1%2F4vxSminaNqeD
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32 — inventory record source_url
|
| ordering_code |
2CSG274761R4051 (M4M 30 MODBUS)
M4M 30 MODBUS (2CSG274761R4051)
|
| phase_count |
3
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
|
| physical_interfaces |
['RS-485 Modbus RTU module', 'Bluetooth Low Energy', '4 programmable I/O']
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
|
| programmable_io_count |
4
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
|
| rated_voltage_v |
46-400 V AC L-N, 80-690 V AC L-L (+20%)
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
|
| voltage_rating_v | 230.0 |
Physical / mechanical
| mounting | DIN-rail |
Environment
| operating_temperature_max_c | 60.0 |
| operating_temperature_min_c | -25.0 |
Interfaces & connectors
| cloud_required |
False
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
|
| communication | RS485 Modbus RTU |
| documented_ports | [{'port_role': 'RS485', 'port_label_from_manual': 'Modbus RTU', 'port_type': 'RS-485 (3-wire A, B, Common)', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 3, 'page': 'Modbus RTU', 'quote': 'Protocol: "3-wire (A, B and Common) polarity dependent bus according to the RS-485 standard"; Topology: Line topology with up to 247 slaves'}, {'port_role': 'BLUETOOTH', 'port_label_from_manual': 'Bluetooth', 'port_type': 'Bluetooth Low Energy', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': None, 'document': 0, 'page': 'Communication Modules by Model', 'quote': 'M4M 30/32 MODBUS | Modbus RTU, Bluetooth'}, {'port_role': 'CT', 'port_label_from_manual': 'current inputs L1, L2, L3, N', 'port_type': 'CT terminals', 'direction': 'input', 'electrical_domain': 'AC', 'quantity': 4, 'document': 0, 'page': 'Current Inputs', 'quote': 'Number of inputs: 4 (L1, L2, L3, N); CT Secondary options: "5 A ... [or] 1 A"'}] |
| protocols |
['Modbus RTU (RS-485)', 'Bluetooth Low Energy']
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
|
Documents
product_page
M4M 30 MODBUS (2CSG274761R4051)
user_manual
M4M 30-32 User Manual 2CSG445042D0201
Recorded conflicts
identity.manufacturer Review required
ABB — stored value
ABB (E-mobility; NA distribution via InCharge Energy) — incoming package
Detected during import wave6-2026-09-batch23
identity.manufacturer Review required
ABB — stored value
ABB (E-mobility; NA distribution via InCharge Energy) — incoming package
Detected during import wave4-2026-09-batch09
Additional documented parameters
Recorded verbatim from the source; no schema field exists for these yet.
| builder_completeness | partial |
| region_notes | One worldwide IEC specification. The variant token records the communication module ordered: ABB also sells the same analyzer with an Ethernet (Modbus TCP/IP), Profibus or BACnet/IP module. |
| withheld:max_connected_devices | "not applicable - measuring device, not a concentrator" |