⚡ANMASystem BuildingAutomation, Network, Monitoring & Analytics
★PREMIUM

Knowledge Base › Smart Meters

ABB (E-mobility; NA distribution via InCharge Energy) M4M 30-M

Official manufacturer GLOBAL verified Sept. 23, 2026

Identity

category smart_meters
manufacturer ABB disputed
model M4M 30-M
product_status active
region GLOBAL
variant Modbus RTU

Electrical

accuracy_class Class 1 (IEC 62053-21) / Class B (EN 50470-3)
accuracy_class_active_energy Class 0,5 acc. to IEC 61557-12:2021
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
auxiliary_supply_v 48 to 240 VAC/VDC ±15%
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
bidirectional True
bidirectional_metering True
ct_secondary_current_a [1, 5]
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
direct_current_max_a not applicable - CT-connected
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
grid_frequency_hz 50-60
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
local_modbus_available True
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
max_current_a 65.0
measurement_directions Four-quadrant - import/export active, reactive and apparent energy
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
measurement_type Current Transformer (CT)
meter_type Front-panel network analyzer, CT-connected (4 current inputs L1, L2, L3, N)
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
mid_approved True
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
modbus_max_bus_length_m 700
MODBUS MANUAL - M4M Network analyzers v.1.05
modbus_max_slaves 247
MODBUS MANUAL - M4M Network analyzers v.1.05
official_manual_url https://library.e.abb.com/public/96e22792897740c3b79b2d758e9667df/2CSG445042D0201_en_M_User%20Manual%20M4M%2030-32.pdf?x-sign=2HBRZEyd492erLmaNYnfoxNzNlcBc8as7MbtkZJHqMbok2Gz5i1%2F4vxSminaNqeD
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32 — inventory record source_url
phase_count 3
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
physical_interfaces ['RS-485 Modbus RTU module', 'Bluetooth Low Energy', '4 programmable I/O']
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
programmable_io_count 4
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
rated_voltage_v 46-400 V AC L-N, 80-690 V AC L-L (+20%)
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
voltage_rating_v 230.0

Physical / mechanical

mounting DIN-rail

Environment

operating_temperature_max_c 60.0
operating_temperature_min_c -25.0

Interfaces & connectors

cloud_required False
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
communication RS485 Modbus RTU
documented_ports [{'port_role': 'RS485', 'port_label_from_manual': 'Modbus RTU', 'port_type': 'RS-485 (3-wire A, B, Common)', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 3, 'page': 'Modbus RTU', 'quote': 'Protocol: "3-wire (A, B and Common) polarity dependent bus according to the RS-485 standard"; Topology: Line topology with up to 247 slaves'}, {'port_role': 'BLUETOOTH', 'port_label_from_manual': 'Bluetooth', 'port_type': 'Bluetooth Low Energy', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': None, 'document': 0, 'page': 'Communication Modules by Model', 'quote': 'M4M 30/32 MODBUS | Modbus RTU, Bluetooth'}, {'port_role': 'CT', 'port_label_from_manual': 'current inputs L1, L2, L3, N', 'port_type': 'CT terminals', 'direction': 'input', 'electrical_domain': 'AC', 'quantity': 4, 'document': 0, 'page': 'Current Inputs', 'quote': 'Number of inputs: 4 (L1, L2, L3, N); CT Secondary options: "5 A ... [or] 1 A"'}]
protocols ['Modbus RTU (RS-485)', 'Bluetooth Low Energy']
M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32

Documents

manual M4M 30-32 User manual 2CSG445042D0201 - Network Analyzer M4M 30 / M4M 30-M / M4M 32
manual MODBUS MANUAL - M4M Network analyzers v.1.05
product_page M4M 30 MODBUS (2CSG274761R4051)
product_page M4M 30-M (ordering code 2CSG239035R4051)
product_page M4M network analyzers - Energy Efficiency devices (Modular DIN-Rail products)

Recorded conflicts

identity.manufacturer Review required
ABB — stored value
ABB (E-mobility; NA distribution via InCharge Energy) — incoming package
Detected during import wave4-2026-09-batch09

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

builder_completenesspartial
region_notesOne worldwide IEC specification. The variant token records the communication module ordered: ABB also sells the same analyzer with an Ethernet (Modbus TCP/IP), Profibus or BACnet/IP module.
withheld:max_connected_devices"not applicable - measuring device, not a concentrator"