ANMASystem BuildingAutomation, Network, Monitoring & Analytics
PREMIUM

Knowledge BaseSmart Meters

Carlo Gavazzi EM24 Ethernet

Official manufacturer global verified Sept. 2, 2026

Unresolved safety-relevant conflict
Two sources give different figures for a value on this product and nobody has resolved it. The specifications below are shown as recorded, but this product must not be treated as verified for engineering purposes until the conflict is closed.

Identity

category smart_meters
manufacturer Carlo Gavazzi
model EM24 Ethernet
oem_ordering_code EM24-DIN.AV2.3.X.E1.X (AV2 = direct 65 A, 3 = three-phase, E1 = Ethernet Modbus TCP/IP) - DISTRIBUTOR-VERIFIED, not stated in any fetched Victron document
product_family Carlo Gavazzi EM24 E1 (Victron-distributed)
product_status active
region global
sku REL200200100

Electrical

accuracy_class_active_energy Class 1 (EN IEC 62053-21)
accuracy_class_reactive_energy Class 2 (EN IEC 62053-23)
accuracy_power ±(0.5% rdg + 1dgt) to ±(1.5% rdg + 1dgt)
base_current Base current (lb) 10 A (AV2); Rated current (In) 5 A (AV5)
ct_ratio_options AV5 variant only: CT transformation ratio max. 6975 (non-MID) / 2615 (MID)
current_connection AV2 = direct connection up to 65 A; AV5 = via 5 A CT (Victron sells the 65 A direct variant per its pricelist description)
display Yes
frequency 50 Hz (MID models)
max_current_victron_spec max 65A/ph
measuring_category Cat. III; UC2
phases Three-phase
power_consumption < 4.7 VA / 2.9 W
rated_voltage_l_l 230 to 400 V (AV2); 400 V (AV5)
rated_voltage_l_n 133 to 230 V (AV2); 230 V (AV5)
refresh_rate 600 ms (Victron selection guide)

Physical / mechanical

dimensions_mm UNKNOWN
din_modules UNKNOWN
material UNKNOWN
weight 400 g (packaging included)

Installation

connection A wired ethernet connection to the local network in such a way that the GX device can reach it
ethernet_distance 100 m
max_clients Maximum 5 client connections
mounting DIN rail

Environment

operating_temperature From -25 to +55 °C
relative_humidity R.H. < 90 % non-condensing @ 40 °C
storage_temperature UNKNOWN

Interfaces & connectors

bluetooth No
ethernet RJ45 connector (10 Base-T, 100 Base-TX)
modbus_rtu No
modbus_tcp Yes - Modbus TCP/IP
rs485 No (this is the Ethernet variant)
ve_direct No
zigbee No

Protection

ip_rating Front: IP50. Terminals: IP20

Certifications

standards ['MID (PF only)', 'UL61010-1', 'EN IEC 61010-1', 'EN 50470-1', 'EN IEC 62053-21', 'EN IEC 62053-23']

Warranty & service

summary UNKNOWN

Documents

manual-html Victron Energy Meter EM24 Ethernet manual - 1. Introduction
manual-html Victron Energy Meter EM24 Ethernet manual - 3. FAQ
manual-pdf {# Located but never retrieved: listed, but deliberately not linked, and it backs no stored value. #} Victron Energy Meters manual (shared, 113406) — located, not retrieved
oem-datasheet Carlo Gavazzi EM24 E1 Datasheet (EM24 E1 DS ENG, 14/02/2025)
pricelist Pricelist Victron 2026 Q1 USD C
product-page Energy Meters product page
selection-guide Victron Energy Meter Selection Guide

Recorded conflicts

electrical.max_current / current_connection Review required
max 65A/ph, direct connection (Victron 2026 Q1 pricelist: "Energy Meter EM24 - 3 phase - max 65A/ph Ethernet"; product page: "EM24 Ethernet - Ethernet - for three-phase max. 65A") — https://latam.victronenergy.com/wp-content/uploads/2026/01/Pricelist-Victron-2026-Q1-USD-C.pdf
5 A per phase, measured via CTs, and "Not stocked by Victron" — https://www.victronenergy.com/upload/documents/Datasheet-Energy-Meters-Selection-Guide-EN.pdf
identity.product_status / stocking Review required
Stocked and priced by Victron (line item with a 2026 Q1 price) — https://latam.victronenergy.com/wp-content/uploads/2026/01/Pricelist-Victron-2026-Q1-USD-C.pdf
"Not stocked by Victron" — https://www.victronenergy.com/upload/documents/Datasheet-Energy-Meters-Selection-Guide-EN.pdf

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

Ethernet cable distance100 m
Maximum Ethernet client connectionsMaximum 5
Order code EM24DIN AV5 3X E1 PFAAV5: 5A CT input variant; 3X: three-phase; E1: Ethernet Modbus TCP/IP; PFA: MID certified with easy connection function
RolesGrid meter and control input for an ESS System; PV Inverter output; AC Genset output; dedicated AC load circuit
documented_relationship:inverter_meter{"to_manufacturer": "Victron Energy", "to_model": "ESS (MultiPlus / Quattro inverter/charger system)", "relationship_type": "inverter_meter", "source": "Victron Energy Meter EM24 Ethernet manual, 1.1 Features", "source_url": "https://www.victronenergy.com/media/pg/Energy_Meter_EM24_Ethernet/en/introduction.html", "confidence": "officially-verified", "notes": "Role: \"As a Grid meter and used as control input for an ESS System\""}

Build a system with this product