Carlo Gavazzi EM530 (EM530DINAV53XS1X)
Official manufacturer global verified Sept. 2, 2026
Identity
| category | smart_meters |
| manufacturer | Carlo Gavazzi |
| model | EM530 (EM530DINAV53XS1X) |
| oem_ordering_code | EM530DINAV53XS1X |
| product_family | Carlo Gavazzi EM530 DIN |
| product_status | active |
| product_status_detail | active (as a Carlo Gavazzi product); NOT stocked by Victron |
| region | global |
| sku | UNKNOWN (no Victron SKU - not a Victron product) |
Electrical
| accuracy_class_active_energy | Class 0.5 S (EN IEC 62053-22); Class B (EN 50470-3 (MID)) |
| accuracy_class_reactive_energy | UNKNOWN |
| ct_ratio_options | AV5: CT transformation ratio 2000 max.; Primary current 10 kA max. RG5 Rogowski current ranges: 600A, 1200A, 2400A; primary current 2.88 kA max. |
| current_connection | Via current transformers. AV5 = 5 A CT input; MV5 = 333 mV input; RG5 = Rogowski coil. Victron's FAQ names the AV5 build (EM530DINAV53XS1X). |
| display | UNKNOWN |
| frequency | 50 Hz (MID); From 45 to 65 Hz (non-MID) |
| measurement_method | TRMS measurements of distorted waveforms |
| measuring_category | UNKNOWN |
| phases | Two-phase (3-wire), Three-phase with neutral (4-wire), Three-phase without neutral (3-wire) |
| power_consumption | < 1.3 W / 2.6 VA |
| rated_current | Rated current (In) input 5 A (AV5); 333 mV (MV5) |
| rated_voltage_l_l | 400 V (MID); 208-415 V (non-MID) |
| rated_voltage_l_n | 230 V (MID); 120-240 V (non-MID) |
| refresh_rate | Modbus RTU refresh <= 100 ms; M-Bus refresh <= 100 ms |
Physical / mechanical
| dimensions_mm | width 90 mm, depth 43.80 mm, height 62.41 mm |
| din_modules | 3-DIN modules |
| material | UNKNOWN |
| weight | 280 g / 0.62 lb (packaging included) |
Installation
| mounting | DIN rail |
| notes | Victron supports this meter in Venus OS software but does not sell it. |
Environment
| operating_temperature | From -25 to +55 °C (standard); From -25 to +70 °C (PFx70) |
| relative_humidity | R.H. < 90 % non-condensing @ 40 °C |
| storage_temperature | From -30 to +70 °C |
Interfaces & connectors
| bluetooth | No |
| ethernet | No |
| m_bus | Available as the M1 output option |
| modbus_rtu | Yes - refresh <= 100 ms |
| modbus_tcp | No |
| rs485 | Yes (S1 output option) |
| ve_direct | No |
Protection
| ip_rating | Front: IP40, Terminals: IP20 |
Certifications
| standards | ['MID certified', 'cULus approved (UL 61010)', 'EN IEC 62053-22', 'EN 50470-3'] |
Warranty & service
| summary | UNKNOWN |
Documents
manual-html
Victron Energy Meter manual - FAQ Q7 (CT meters)
oem-datasheet
Carlo Gavazzi EM530 Datasheet (EM530 DS ENG)
selection-guide
Victron Energy Meter Selection Guide
Additional documented parameters
Recorded verbatim from the source; no schema field exists for these yet.
| 333 mV input option MV5 | Primary current 10 kA max. |
| M-Bus output | M1 output option, refresh <= 100 ms |
| Order code structure | EM530 DIN AV5 3X [O1/S1/M1] [70]; modifiers PFA, PFB, PFC, PFD, PFE; 70 suffix denotes max operating temperature upgrade |
| Rogowski coil option RG5 | Primary current 2.88 kA max.; current ranges 600A, 1200A, 2400A |
| documented_relationship:gateway_device | {"to_manufacturer": "Victron Energy", "to_model": "GX device / Venus OS", "relationship_type": "gateway_device", "source": "Victron Energy Meter manual, FAQ Q7", "source_url": "https://www.victronenergy.com/media/pg/Energy_Meter_EM24_Ethernet/en/faq.html", "confidence": "officially-verified", "notes": "Victron supports this Carlo Gavazzi CT-input meter in Venus OS even though it does not sell it. The EM530 is the recommended route when current transformers are required."} |
| identity.product_status | active (as a Carlo Gavazzi product); NOT stocked by Victron |