ANMASystem BuildingAutomation, Network, Monitoring & Analytics
PREMIUM

Knowledge BaseSmart Meters

Carlo Gavazzi EM530 (EM530DINAV53XS1X)

Official manufacturer global verified Sept. 2, 2026

Identity

category smart_meters
manufacturer Carlo Gavazzi
model EM530 (EM530DINAV53XS1X)
oem_ordering_code EM530DINAV53XS1X
product_family Carlo Gavazzi EM530 DIN
product_status active
product_status_detail active (as a Carlo Gavazzi product); NOT stocked by Victron
region global
sku UNKNOWN (no Victron SKU - not a Victron product)

Electrical

accuracy_class_active_energy Class 0.5 S (EN IEC 62053-22); Class B (EN 50470-3 (MID))
accuracy_class_reactive_energy UNKNOWN
ct_ratio_options AV5: CT transformation ratio 2000 max.; Primary current 10 kA max. RG5 Rogowski current ranges: 600A, 1200A, 2400A; primary current 2.88 kA max.
current_connection Via current transformers. AV5 = 5 A CT input; MV5 = 333 mV input; RG5 = Rogowski coil. Victron's FAQ names the AV5 build (EM530DINAV53XS1X).
display UNKNOWN
frequency 50 Hz (MID); From 45 to 65 Hz (non-MID)
measurement_method TRMS measurements of distorted waveforms
measuring_category UNKNOWN
phases Two-phase (3-wire), Three-phase with neutral (4-wire), Three-phase without neutral (3-wire)
power_consumption < 1.3 W / 2.6 VA
rated_current Rated current (In) input 5 A (AV5); 333 mV (MV5)
rated_voltage_l_l 400 V (MID); 208-415 V (non-MID)
rated_voltage_l_n 230 V (MID); 120-240 V (non-MID)
refresh_rate Modbus RTU refresh <= 100 ms; M-Bus refresh <= 100 ms

Physical / mechanical

dimensions_mm width 90 mm, depth 43.80 mm, height 62.41 mm
din_modules 3-DIN modules
material UNKNOWN
weight 280 g / 0.62 lb (packaging included)

Installation

mounting DIN rail
notes Victron supports this meter in Venus OS software but does not sell it.

Environment

operating_temperature From -25 to +55 °C (standard); From -25 to +70 °C (PFx70)
relative_humidity R.H. < 90 % non-condensing @ 40 °C
storage_temperature From -30 to +70 °C

Interfaces & connectors

bluetooth No
ethernet No
m_bus Available as the M1 output option
modbus_rtu Yes - refresh <= 100 ms
modbus_tcp No
rs485 Yes (S1 output option)
ve_direct No

Protection

ip_rating Front: IP40, Terminals: IP20

Certifications

standards ['MID certified', 'cULus approved (UL 61010)', 'EN IEC 62053-22', 'EN 50470-3']

Warranty & service

summary UNKNOWN

Documents

manual-html Victron Energy Meter manual - FAQ Q7 (CT meters)
oem-datasheet Carlo Gavazzi EM530 Datasheet (EM530 DS ENG)
selection-guide Victron Energy Meter Selection Guide

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

333 mV input option MV5Primary current 10 kA max.
M-Bus outputM1 output option, refresh <= 100 ms
Order code structureEM530 DIN AV5 3X [O1/S1/M1] [70]; modifiers PFA, PFB, PFC, PFD, PFE; 70 suffix denotes max operating temperature upgrade
Rogowski coil option RG5Primary current 2.88 kA max.; current ranges 600A, 1200A, 2400A
documented_relationship:gateway_device{"to_manufacturer": "Victron Energy", "to_model": "GX device / Venus OS", "relationship_type": "gateway_device", "source": "Victron Energy Meter manual, FAQ Q7", "source_url": "https://www.victronenergy.com/media/pg/Energy_Meter_EM24_Ethernet/en/faq.html", "confidence": "officially-verified", "notes": "Victron supports this Carlo Gavazzi CT-input meter in Venus OS even though it does not sell it. The EM530 is the recommended route when current transformers are required."}
identity.product_statusactive (as a Carlo Gavazzi product); NOT stocked by Victron