ANMASystem BuildingAutomation, Network, Monitoring & Analytics
PREMIUM

Knowledge BaseSmart Meters

Carlo Gavazzi EM540

Official manufacturer global verified Sept. 2, 2026

Identity

category smart_meters
manufacturer Carlo Gavazzi
model EM540
oem_ordering_code EM540DINAV23XS1X
product_family Carlo Gavazzi EM540 (Victron-distributed)
product_status active
region global
sku REL200100100

Electrical

accuracy_active_power ± 1% rdg (1.0-65.0 A, PF 0.5-1-0.8)
accuracy_class_active_energy Class 1 EN IEC 62053-21; Class B EN 50470-3 (MID)
accuracy_class_reactive_energy Class 2 (EN IEC 62053-23)
accuracy_reactive_power ± 2% rdg to ± 2.5% rdg
base_current 5 A
ct_ratio_options Not applicable - direct connection
current_connection Direct connection (no CT required)
display Yes - the EM540 has a display (contrast with the ET meters, which have none)
energy_totalisation In the EM540, the energy imported and exported is counted as a total power, with net differential readings from each phase cancelling each other out.
frequency From 45 to 65 Hz (non-MID); 50 Hz (MID)
max_current 65 A
max_current_victron_spec max. 65A/phase
measuring_category UNKNOWN
minimum_current 0.25 A
phases Two-phase (3-wire), Three-phase with neutral (4-wire), Three-phase without neutral (3-wire), Wild leg system
power_consumption < 1.3 W / 2.6 VA
rated_voltage_l_l 208 to 415 V (non-MID)
rated_voltage_l_n 120 to 240 V (non-MID)
refresh_rate <= 100 ms (Modbus RTU refresh time); Victron selection guide states 100 ms

Physical / mechanical

dimensions_mm UNKNOWN (width 90 mm)
din_modules 3-DIN modules
material UNKNOWN
terminals_measuring_inputs 2.5 to 16 mm2
terminals_neutral 0.06 to 2.5 mm2
weight 370 g / 0.82 lb (packaging included)

Installation

mounting DIN rail
phase_configuration Select either Role or Phase type and press the space bar to make changes
plug_and_play The EM540 is plug and play and its RS485 settings are already configured to the correct parameters for connection to a GX device via the RS485 to USB interface.
rs485_wiring Orange = Data + to terminal 8; Yellow = Data - to terminal 9; Black = GND to terminal 10

Environment

operating_temperature From -25 to +55 °C (standard); -25 to +70 °C (PFx70 models)
relative_humidity R.H. < 90 % non-condensing @ 40 °C
storage_temperature -25 to +70 °C

Interfaces & connectors

bluetooth No
ethernet No
modbus_rtu Yes - baud 9.6/19.2/38.4/57.6/115.2 kbps; addresses from 1 to 247; refresh time <= 100 ms
modbus_tcp No
rs485 Yes
ve_direct No
zigbee Optional via Victron Zigbee to USB / Zigbee to RS485 converters

Protection

ip_rating Front: IP40; Terminals: IP20

Certifications

standards ['EN IEC 61010-1', 'EN IEC 62053-21', 'EN IEC 61557-12', 'MID certified (select models)', 'cULus approved (UL 61010)']

Warranty & service

summary UNKNOWN

Documents

manual-html Victron Energy Meter EM540 manual - FAQ
manual-html Victron Energy Meter EM540 manual - Installation and Configuration
manual-pdf Energy Meter Manual EM540 (shared, 113406)
oem-datasheet Carlo Gavazzi EM540 Datasheet (EM540 DS ENG, 01/04/2025)
pricelist Pricelist Victron 2026 Q1 USD C
product-page Energy Meters product page
selection-guide Victron Energy Meter Selection Guide

Recorded conflicts

electrical.current_connection Review required
Direct connection, no CT required (Carlo Gavazzi EM540 datasheet: EM540DINAV23XS1X is the AV2 direct-connect 65 A variant) — https://www.gavazziautomation.com/fileadmin/images/PIM/DATASHEET/ENG/EM540_DS_ENG.pdf
"CTs" as the measurement type for EM540 — https://www.victronenergy.com/upload/documents/Datasheet-Energy-Meters-Selection-Guide-EN.pdf

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

MID certificationClass B EN 50470-3 (MID) on MID variants
Neutral terminal wire size0.06 to 2.5 mm2
PFx70 variantoperating temperature upgraded to -25 to +70 °C
Wild leg systemsupported managed system type
cULus approvedUL 61010
documented_relationship:inverter_meter{"to_manufacturer": "Victron Energy", "to_model": "ESS (MultiPlus / Quattro inverter/charger system)", "relationship_type": "inverter_meter", "source": "Victron Energy Meter manual, Features / FAQ Q10", "source_url": "https://www.victronenergy.com/media/pg/Energy_Meter_EM540/en/faq.html", "confidence": "officially-verified", "notes": "Role: grid meter and control input for an ESS System. FAQ Q10: \"Energy Meters are intended to supplement a Victron Inverter/Charger in the system.\""}