Identity

category smart_meters
manufacturer Carlo Gavazzi
model ET112
oem_ordering_code ET112-DIN.AV01.X.S1.X
product_family Carlo Gavazzi ET112 (Victron-distributed)
product_status active
region global
sku REL300100000

Electrical

accuracy_class_active_energy Class 1 according to EN62053-21
accuracy_class_reactive_energy Class 2 according to EN62053-23
accuracy_current_voltage ±0.5% RDG
base_current 5 A
ct_ratio_options Not applicable - direct connection
current_connection Direct / Shunt (no CT)
display No display - only an LED which blinks in case of active communication
frequency 45 to 65Hz
insulation 4000 VAC RMS between measuring inputs and digital/serial output
max_continuous_current 100A, @ 50Hz
max_current_victron_spec max 100A
measuring_category Cat. III (overvoltage category)
minimum_current 0.25A
nominal_voltage 230VLN AC (AV0 option), 120 VLN (AV1 option); Victron ships the AV0 (230 VLN) variant
phases 1-phase 2-wire
power_consumption <= 1.0W, <= 8VA
rated_current 5(100)A (direct connection)
refresh_rate 750 ms (Victron selection guide); 1 sec data refresh (Carlo Gavazzi datasheet)
self_power_supply_range 230VAC VL-N, -30% +20% (AV0)
temperature_drift <=200ppm/°C

Physical / mechanical

dimensions_mm 35 x 63 x 90 mm
din_modules 2-DIN module
material Noryl, self-extinguishing: UL 94 V-0
screw_torque_measuring Max. screw tightening torque: 2.8 Nm
screw_torque_other Min./Max. screws tightening torque: 0.5 Nm
terminals_measuring_inputs max. 25 mm2, min. 5 mm2
terminals_other 1.5 mm2
weight Approx. 160 g (packing included)

Installation

max_cable_length The RS485 to USB interface cable between the GX device and the Energy Meter can be extended up to 100 meters; make sure that the extensions of the Data+ (orange) and Data- (yellow) wires form a twisted pair.
mounting DIN rail
multiple_meters To connect multiple Energy Meters, wire each meter to a separate RS485 to USB interface, which are then each plugged into a separate USB socket on the GX device.
rs485_wiring Data+ orange wire to terminal 4; Data- yellow wire to terminal 5; GND black wire to terminal 6

Environment

operating_temperature -25 to +65 °C, indoor
relative_humidity R.H. from 0 to 90% noncondensing @ 40°C
storage_temperature -30°C to +80°C

Interfaces & connectors

bluetooth No
ethernet No
modbus_rtu Yes - ModBus RTU (slave function); baud 9.6, 19.2, 38.4, 57.6, 115.2 kbaud; address 1 to 247 (default: 01); maximum 247 transceivers on the same bus
modbus_tcp No
rs485 Yes - RS485 Modbus port
ve_direct No
zigbee Optional via Victron Zigbee to USB converter (ASS300420200) and Zigbee to RS485 converter (ASS300420100); Venus OS v2.54 minimum for the new type Zigbee converters

Protection

ip_rating Protection degree (front): IP20

Certifications

standards ['CE', 'EN62052-11 (Safety)', 'EN62053-21 (Metrology)', 'EMC according to EN62052-11']

Warranty & service

summary UNKNOWN

Documents

manual-html Victron Energy Meter ET112 manual - 1. Introduction
manual-html Victron Energy Meter ET112 manual - 2. Installation and Configuration
manual-html Victron Energy Meter ET112 manual - 3. FAQ
manual-pdf {# Located but never retrieved: listed, but deliberately not linked, and it backs no stored value. #} Victron Energy Meters manual (shared, 113406) — located, not retrieved
oem-datasheet Carlo Gavazzi ET112 Datasheet (ET112 DS ENG)
pricelist Pricelist Victron 2026 Q1 USD C
product-page Energy Meters VM-3P75CT, VM-3P5A, ET112, ET340, EM24 Ethernet & EM540
selection-guide Victron Energy Meter Selection Guide

Recorded conflicts

electrical.refresh_rate Review required
750 ms — https://www.victronenergy.com/upload/documents/Datasheet-Energy-Meters-Selection-Guide-EN.pdf (Victron selection guide)
1 sec — https://www.gavazziautomation.com/fileadmin/images/PIM/DATASHEET/ENG/ET112_DS_ENG.PDF (Carlo Gavazzi "Data Refresh 1sec")

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

Combining three ET112s for 3-phaseNo. Use a real 3-phase meter.
Data Refresh1sec
Max. screw tightening torque (measuring inputs)2.8 Nm
Modbus address changeabilitySince there is no display, the modbus address can no longer be changed on the meter.
Ordering code position AV0230VLN AC - 5(100)A (Direct connection)
Ordering code position S1RS485 Modbus port
Temperature Drift<=200ppm/°C
documented_relationship:gateway_device{"to_manufacturer": "Victron Energy", "to_model": "GX device (Cerbo GX / Venus OS family)", "relationship_type": "gateway_device", "source": "Victron Energy Meter ET112 manual, 1. Introduction", "source_url": "https://www.victronenergy.com/media/pg/Energy_Meter_ET112/en/introduction.html", "confidence": "officially-verified", "notes": "\"The Victron ET112 is a standard device to measure the power and energy of a single-phase application. Its data will be displayed on a GX device and our VRM portal.\""}
documented_relationship:inverter_meter{"to_manufacturer": "Victron Energy", "to_model": "ESS (MultiPlus / Quattro inverter/charger system)", "relationship_type": "inverter_meter", "source": "Victron Energy Meter manual, Features", "source_url": "https://www.victronenergy.com/media/pg/Energy_Meter_ET112/en/introduction.html", "confidence": "officially-verified", "notes": "Role 1: \"As a Grid meter and used as control input for an ESS System\". FAQ Q10: \"Energy Meters are intended to supplement a Victron Inverter/Charger in the system.\""}

Build a system with this product