ANMASystem BuildingAutomation, Network, Monitoring & Analytics
PREMIUM

Knowledge BaseSmart Meters

FoxESS Smart Meter DTSU666 (three-phase, direct and 200A-CT variants)

Official manufacturer global (EN datasheet) verified Sept. 1, 2026

Identity

category smart_meters
ean UNKNOWN
manufacturer FoxESS
market_version UNKNOWN
model Smart Meter DTSU666 (three-phase, direct and 200A-CT variants)
mpn DTSU666
product_family FoxESS Smart Meter (DDSU666 single-phase / DTSU666 three-phase)
product_status active
region global (EN datasheet)
release_year UNKNOWN
sku UNKNOWN

Electrical

ct_ratio direct variant: N/A; CT variant: 200A CTs ('3 CT 200A(1m)')
electrical_ratings {'rated_voltage_vac': '304 ~ 499 (line) / 176 ~ 288 (phase)', 'rated_current_a': '0 ~ 200', 'accuracy_class': 'Class 1', 'power_consumption_w': '<=1', 'frequency_accuracy_hz': '+/-0.01'}
export_limitation_support UNKNOWN
max_current_a 80 (direct variant); 200 via CT (DTSU666 1.5(6)A with 3x 200A CT variant)
measurement_type direct (base variant) / CT-based (200A CT variant)
modbus_rtu true (RS485, 9600 baud)
modbus_tcp False
phase_type three-phase (3P4W)
rs485 True
sources [{'url': 'https://www.fox-ess.com/download/upfiles/EN-Smart-Meter-Datasheet-V1.1-20241128.pdf', 'title': 'FoxESS Smart Meter Datasheet (single-phase/three-phase)', 'doc_type': 'datasheet', 'publisher': 'FoxESS', 'revision': 'V1.1 2024/11/28', 'doc_date': '2024-11', 'language': 'en', 'accessed': '2026-09-01', 'confidence': 'officially-verified'}]
supported_inverter_brands_models FoxESS inverters (sold as FoxESS Smart Meter; pairing per-series not enumerated in the fetched datasheet)

Physical / mechanical

cable_gland_sizes N/A
depth_mm 85
din_rail_type DIN35 rail
enclosure_material UNKNOWN
height_mm 100
housing_color UNKNOWN
mounting_hole_spacing_mm N/A (DIN rail)
mounting_type ['DIN-rail']
screw_sizes UNKNOWN
shipping_weight_kg UNKNOWN
torque_specs UNKNOWN
weight_kg 1.5
FoxESS Smart Meter Datasheet (single-phase / three-phase) V1.1 — DTSU666 column 'Weight 1.5 kg'
width_mm 72
FoxESS Smart Meter Datasheet (single-phase / three-phase) V1.1 — DTSU666 column 'Dimensions 72*100*85 mm'

Installation

ct_note CT variant supplied as '3 CT 200A(1m)' - three 200 A current transformers with 1 m leads
indoor_outdoor indoor (distribution enclosure); no IP rating stated in the datasheet
max_installation_altitude_m UNKNOWN
mounting_orientation DIN35 rail mounting inside a distribution board
surface_requirements 35 mm DIN rail

Environment

cooling_method natural convection
ip_rating UNKNOWN
max_altitude_m UNKNOWN
noise_level_db N/A
operating_temperature_c -25 ~ +55
relative_humidity 5 ~ 95 % (Non-condensing)
storage_temperature_c -40 ~ +70

Interfaces & connectors

modbus_rtu yes (RS485, 9600 bps)
modbus_tcp False
protocol_notes Datasheet communication row: 'RS485' at 9600 bps
rs485 yes

Controls & display

buttons UNKNOWN
display_type LCD display
leds UNKNOWN
local_display True
touchscreen False

Documents

datasheet FoxESS Smart Meter Datasheet (single-phase / three-phase) V1.1 rev V1.1

Recorded conflicts

max_current_a Review required
80 (direct variant); 200 via CT — value currently stored on the record
0 ~ 200 A — FoxESS Smart Meter datasheet V1.1, DTSU666 column 'Rated/Max Current 0 ~ 200 A' (targeted re-extraction 2026-09-02)
the datasheet's single current row appears to cover the CT-fed variant; the 80 A direct figure may come from a different row/revision or from the DDSU666 column. Not resolved.
max_current_a Review required
80 (direct variant); 200 via CT — value currently stored on the record
0 ~ 200 A — FoxESS Smart Meter datasheet V1.1, DTSU666 column 'Rated/Max Current 0 ~ 200 A' (targeted re-extraction 2026-09-02)
the datasheet's single current row appears to cover the CT-fed variant; the 80 A direct figure may come from a different row/revision or from the DDSU666 column. Not resolved.

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

CT variant3 CT 200A(1m)
Power consumption<=1 W

Build a system with this product