ANMASystem BuildingAutomation, Network, Monitoring & Analytics
PREMIUM

Knowledge BaseSmart Meters

Fronius Smart Meter TS 65A-3

Official manufacturer EU verified Sept. 2, 2026

Identity

category smart_meters
document_number 42,0426,0349 (operating instructions)
ean UNKNOWN
generation Smart Meter TS
manufacturer Fronius
market_version EU (CE)
model Smart Meter TS 65A-3
mpn UNKNOWN
product_family Fronius Smart Meter TS (TS 65A-3 / TS 100A-1 / TS 5kA-3)
product_revision UNKNOWN
product_status active
region EU
release_year UNKNOWN
sku UNKNOWN

Electrical

accuracy_class 1
Fronius Smart Meter TS 65A-3 - Technical data — General technical data, 'Accuracy class 1'
ct_ratio N/A (direct-connect meter)
electrical_extra {'nominal_voltage': '208 - 400 V (L-L)', 'voltage_operating_range_v': '166.4 - 480', 'nominal_current_a': 5, 'max_current_a': 65, 'frequency_hz': '50 - 60', 'frequency_tolerance_hz': '45 - 65', 'power_consumption_voltage_path': '<= 10 VA', 'self_consumption_current_path': '<= 1 W', 'starting_current_ma': 20, 'measurement': "bidirectional; configuration mode B 'measures imported and exported energy separately'"}
export_limitation_support True
max_current_a 65
measurement_type direct
modbus_rtu True
modbus_tcp UNKNOWN (the meter itself is Modbus RTU over RS485 only; TCP is provided by the connected Fronius inverter / Datamanager, not by the meter)
phase_type three-phase (2-phase variant configurations also documented)
rs485 True
supported_inverter_brands_models ['Fronius SnapINverter (Primo, Symo)', 'Fronius GEN24 family, via Fronius Datamanager 2.0']

Physical / mechanical

depth_mm 63
Fronius Smart Meter TS 65A-3 - Technical data — General technical data, 'Dimension / depth 63 mm'
din_rail_type 35 mm DIN rail ('Can be snapped onto 35 mm DIN rail')
enclosure_material UNKNOWN
height_mm 91.5
Fronius Smart Meter TS 65A-3 - Technical data — General technical data, 'Dimension / height 91,5 mm'
housing_color UNKNOWN
module_width 3 modules according to DIN 43880
mounting_type ['DIN-rail']
screw_sizes UNKNOWN
shipping_weight_kg UNKNOWN
terminal_locations measuring inputs (phase/neutral) and data output (RS485) terminals; 2x protective cover and 2x connection cover with seal wires supplied
torque_specs measuring input terminals: max. 2.8 Nm; data output terminals: max. 0.4 Nm
Fronius Smart Meter TS 65A-3 - Operating instructions (42,0426,0349) — Technical data, terminal specifications - 'Recommended torque max. 2.8 Nm' (measuring) and 'max. 0.4 Nm' (data)
weight_kg 0.24
width_mm 53.8
Fronius Smart Meter TS 65A-3 - Technical data — General technical data, 'Dimension / width 53,8 mm'

Installation

data_cable_requirement 'Use network cables of type CAT5 or higher'
indoor_outdoor indoor (distribution board; IP51 housing, IP20 connections)
installation_note 'The Fronius Smart Meter TS is a fixed piece of equipment for public grids of TN/TT systems and records the self-consumption or individual loads in the system.' Not suitable for the power supply of life-sustaining medical devices or for billing costs to subtenants.
max_cable_length_to_inverter_m 300
mounting_orientation DIN rail in a household/sub distribution board
surface_requirements 35 mm DIN rail
termination 'The terminating resistor is integrated in the Fronius Smart Meter TS and is manufactured with a bridge between the M and T connections'
wiring_topologies 3 phases, 4 conductors; 3 phases, 3 conductors; 2 phases, 3 conductors
Fronius Smart Meter TS 65A-3 - Operating instructions (42,0426,0349) — Connection variants / configuration chapter

Environment

cooling_method natural convection (passive)
ik_rating UNKNOWN
ip_rating IP51 housing, IP20 connections
Fronius Smart Meter TS 65A-3 - Operating instructions (42,0426,0349) — Technical data, 'Degree of Protection IP51 housing, IP20 connections'
max_altitude_m UNKNOWN
nema_rating UNKNOWN
noise_level_db none
operating_temperature_c -25 to +55 (operating instructions); fronius.com technical data page states '-25 degC - +65 degC' operating range - see data_conflicts
overvoltage_installation_category III
pollution_degree 2
relative_humidity UNKNOWN
storage_temperature_c -30 to +80

Interfaces & connectors

bluetooth False
can False
cellular False
data_output_terminals min. 0.05 mm2, recommended torque max. 0.4 Nm
ethernet False
measuring_input_terminals min. 1 mm2 / max. 16 mm2, recommended torque max. 2.8 Nm
modbus_rtu True
modbus_tcp False
protocol_notes Connects to Fronius SnapINverter systems via a Fronius inverter or Fronius Datamanager 2.0 plus a Fronius data interface; on GEN24 inverters it is configured on the M0 / M1 Modbus inputs. Max. 3 secondary meters on SnapINverter systems; 'Use no more than 7 secondary meters in the system' on GEN24.
rs485 RS485 / Modbus RTU. Baud rate 300, 2400, 9600 bit/s (default 9600); data bits 8; stop bit 1; parity none / odd / even; Modbus addresses 1 - 255; response time <= 200 ms; integrated terminating resistor (bridge M-T)
Fronius Smart Meter TS 65A-3 - Operating instructions (42,0426,0349) — Technical data, RS485 interface parameters
usb False
wifi False
zigbee False

Controls & display

buttons Up, Down, Enter - 'Up' and 'Down' scroll screens and adjust values; 'Enter' confirms selections and accesses settings menus
display_type LCD display with menu navigation
leds UNKNOWN
local_display True
mobile_app Fronius Solar.web (via the inverter)
touchscreen False
web_interface via the inverter user interface

Protection

overload_short_term 1950 A @ 10 ms
overvoltage_category III (installation category)
protection_class UNKNOWN

Certifications

emc []
grid_codes []
metering ['EN IEC 62053-21', 'EN IEC 62053-23', 'EN 50470']
other ['EU Directive 2012/19/EU (WEEE)', 'EU Directive 2011/65/EU (RoHS)']
regional ['CE']
safety ['EN IEC 62052-11', 'EN 60529', 'IEC 60947-1', 'IEC 60947-3']

Warranty & service

conditions UNKNOWN
design_life_years UNKNOWN
standard_years UNKNOWN

Documents

datasheet Fronius Smart Meter TS 65A-3 - Technical data rev UNKNOWN
user-manual Fronius Smart Meter TS 65A-3 - Operating instructions (42,0426,0349) rev 42,0426,0349

Recorded conflicts

environment.operating_temperature_c Review required
-25 to +55 degC — Fronius Smart Meter TS 65A-3 operating instructions 42,0426,0349, Technical data ('Operating Temperature -25 bis +55 degC'), fetched 2026-09-02
-25 degC - +65 degC — fronius.com technical data page 'Fronius Smart Meter TS 65A-3', General technical data, 'Operating range', fetched 2026-09-02
the technical-data page's 'Operating range' may cover a wider limiting range than the manual's operating temperature, or the documents are of different revisions
environment.operating_temperature_c Review required
-25 to +55 degC — Fronius Smart Meter TS 65A-3 operating instructions 42,0426,0349, Technical data ('Operating Temperature -25 bis +55 degC'), fetched 2026-09-02
-25 degC - +65 degC — fronius.com technical data page 'Fronius Smart Meter TS 65A-3', General technical data, 'Operating range', fetched 2026-09-02
the technical-data page's 'Operating range' may cover a wider limiting range than the manual's operating temperature, or the documents are of different revisions

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

Housing3 modules according to DIN 43880
Installation categoryIII
Maximum cable length between the Fronius inverter and Smart Meter300 meters
Overload (short-term)1950A@10ms
Pollution degree2
Response time<= 200 ms
Secondary meter limit (GEN24)Use no more than 7 secondary meters in the system
Secondary meter limit (SnapINverter)Up to 3 secondary meters maximum
Starting current20 mA

Build a system with this product