ANMASystem BuildingAutomation, Network, Monitoring & Analytics
PREMIUM

Knowledge BaseSmart Meters

GoodWe GM3000

Official manufacturer global EN documentation verified Sept. 2, 2026

Identity

category smart_meters
ean UNKNOWN
generation UNKNOWN
manufacturer GoodWe
market_version UNKNOWN
model GM3000
mpn UNKNOWN
product_family GoodWe Smart Meter (GM1000 / GM1000D / GM3000)
product_revision UNKNOWN
product_status active
region global EN documentation
release_year UNKNOWN
sku GM3000

Electrical

accuracy_class Voltage/Current Class 1; Active Energy Class 1; Reactive Energy Class 2
(GM1000D/GM3000/GM1000) Quick Installation Guide Smart Meter — quick installation guide accuracy rows
ct_count 3
ct_ratio 120A/40mA
(GM1000D/GM3000/GM1000) Quick Installation Guide Smart Meter — GM3000 column: 'CT in: 120A/40mA', range '0.48A~120A'
export_limitation_support UNKNOWN
max_current_a 120 (CT-based: 'CT in: 120A/40mA', range 0.48A~120A)
measurement_type CT-based
modbus_rtu True
modbus_tcp False
phase_type three-phase
power_consumption_w <3
rated_frequency_hz 50/60
rated_voltage_v 230 Vac line-to-neutral / 400 Vac line-to-line; operating range 0.88Un-1.1Un
(GM1000D/GM3000/GM1000) Quick Installation Guide Smart Meter — quick installation guide, GM3000 '230' Vac L-N / '400' Vac L-L, range '0.88Un-1.1Un'
rs485 True
sources [{'url': 'https://solarmagazine.nl/u/webshop/goodwe-smartmeter-datasheet-en.pdf', 'title': 'GoodWe Smart Meter Datasheet (GM1000/GM1000D/GM3000)', 'doc_type': 'datasheet-mirror (official GoodWe datasheet hosted by distributor)', 'publisher': 'GoodWe (hosted by Solar Magazine NL)', 'revision': 'GoodWe-Smart meter-20201119-EN-V5.0', 'doc_date': '2020-11', 'language': 'en', 'accessed': '2026-09-01', 'confidence': 'manufacturer-documented'}]
supported_inverter_brands_models GoodWe hybrid inverters (ES G2 user manual: 'Recommended model: GM1000 and GM3000')

Physical / mechanical

depth_mm 66.5
din_rail_type DIN rail, 2-module housing
enclosure_material UNKNOWN
height_mm 85
housing_color UNKNOWN
mounting_type ['DIN-rail']
screw_sizes UNKNOWN
shipping_weight_kg UNKNOWN
terminal_locations UNKNOWN
torque_specs UNKNOWN
weight_kg 0.45
(GM1000D/GM3000/GM1000) Quick Installation Guide Smart Meter — quick installation guide, GM3000 weight 450 g
width_mm 36
(GM1000D/GM3000/GM1000) Quick Installation Guide Smart Meter — quick installation guide, physical specification '36*85*66.5' mm, 2-module housing

Installation

clearance_bottom_mm UNKNOWN
clearance_front_mm UNKNOWN
clearance_left_mm UNKNOWN
clearance_right_mm UNKNOWN
clearance_top_mm UNKNOWN
indoor_outdoor indoor (IP20)
max_installation_altitude_m 2000
mounting_orientation DIN-rail mounted inside a distribution board

Environment

cooling_method natural convection (no active cooling)
ik_rating UNKNOWN
ip_rating IP20
(GM1000D/GM3000/GM1000) Quick Installation Guide Smart Meter — quick installation guide, 'IP20'
max_altitude_m 2000
nema_rating UNKNOWN
noise_level_db UNKNOWN
operating_temperature_c -25 ~ 60
(GM1000D/GM3000/GM1000) Quick Installation Guide Smart Meter — quick installation guide, '-25~60' degC
relative_humidity 0 ~ 95% (non-condensing)
storage_temperature_c -30 ~ 70

Interfaces & connectors

can UNKNOWN
ethernet UNKNOWN
modbus_rtu True
modbus_tcp False
protocol_notes RS485 / Modbus protocol. Quick Installation Guide does not state terminal screw sizes, torque, RS485 pin numbers or baud rate.
rs485 RS485, max communication distance 1000 m
wifi UNKNOWN

Controls & display

buttons Reset button
display_type none
leds 3 LED
local_display False
touchscreen False

Documents

datasheet GoodWe Smart Meter Datasheet (GM1000/GM1000D/GM3000) rev GoodWe-Smart meter-20201119-EN-V5.0
product-page Single and 3 Phase Smart Meter product page (GoodWe EMEA) rev UNKNOWN
quick-start (GM1000D/GM3000/GM1000) Quick Installation Guide Smart Meter rev V1.3 -2023-11-30

Recorded conflicts

communication_cable_max_length Review required
100 m — GoodWe Smart Meter Datasheet V5.0 (2020-11-19), 'Communication Cable Max.Length 100m'
1000 m — GoodWe (GM1000D/GM3000/GM1000) Quick Installation Guide V1.3 (2023-11-30), RS485 'Distance 1000 m'
document revision difference (2020 datasheet vs 2023 quick installation guide); the 100 m figure may be a recommended installation limit and 1000 m the RS485 bus maximum
communication_cable_max_length Review required
100 m — GoodWe Smart Meter Datasheet V5.0 (2020-11-19), 'Communication Cable Max.Length 100m'
1000 m — GoodWe (GM1000D/GM3000/GM1000) Quick Installation Guide V1.3 (2023-11-30), RS485 'Distance 1000 m'
document revision difference (2020 datasheet vs 2023 quick installation guide); the 100 m figure may be a recommended installation limit and 1000 m the RS485 bus maximum

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

Communication distance1000 m
Metering disclaimerThe measured energy yield and electricity consumption are for reference only and cannot be used as a basis for calculating electricity fees.
Number of current transformersGM3000: 3 CTs

Build a system with this product