Huawei DDSU666-H
Manufacturer documented global verified Sept. 3, 2026
Identity
| category | smart_meters |
| ean | UNKNOWN |
| legal_entity_printed | HUAWEI (Manufacturer field on the Huawei spec page) |
| manufacturer | Huawei |
| market_version | single-phase (1P2W) |
| marketing_name | Smart Power Sensor |
| model | DDSU666-H |
| mpn | UNKNOWN |
| product_family | Huawei Smart Power Sensor (DDSU666-H / DTSU666-H) |
| product_status | active |
| region | global |
| sku | UNKNOWN |
Electrical
| accuracy_class | voltage +/- 0.5%; current/power/energy +/- 1% (datasheet 'Voltage Accuracy', 'Current/Power/Energy Accuracy'). A formal IEC accuracy class is not stated. |
| accuracy_current_voltage_pct | ± 0.5% |
| accuracy_frequency_hz | ± 0.01 Hz |
| accuracy_power_energy_pct | ± 1% |
| ct_ratio | 100 A / 40 mA |
| ct_supplied | 1 CT 100 A / 40 mA (5 m / 16.4 ft.) |
| export_limitation_support | True |
| frequency_hz | UNKNOWN |
| max_current_a |
100 (datasheet 'Current Range 0 ~ 100A') - now confirmed from a fetched Huawei document, replacing the previous distributor-sourced note
Huawei Smart Power Sensor datasheet (DDSU666-H / DTSU666-H), Version No.: 02-(20181229) — DDSU666-H column, 'Current Range 0 ~ 100A'
|
| measurement_current_a | 0 - 100 A |
| measurement_method | external current transformer (not direct) |
| measurement_phase_voltage_v | 176 V AC - 288 V AC |
| measurement_type | UNKNOWN (datasheet does not state direct-connected vs CT-operated) |
| modbus_rtu | True |
| modbus_tcp | UNKNOWN |
| phase_configuration | single-phase |
| phase_type |
single-phase
Huawei Smart Power Sensor datasheet (DDSU666-H / DTSU666-H), Version No.: 02-(20181229) — DDSU666-H column, 'Power Grid Type 1P2W'
|
| power_consumption_w |
<= 0.8
disputed
Huawei Smart Power Sensor datasheet (DDSU666-H / DTSU666-H), Version No.: 02-(20181229) — DDSU666-H column, 'Power Consumption <= 0.8W'
|
| power_grid_type | 1P2W |
| rs485 | True |
| sources | [{'url': 'https://ske-solar.com/productdata/SUN2000-L1/02_Manuals/User%20Manual_SUN2000-2-6KTL-L1_V20_2024-05-30_EN.pdf', 'title': 'SUN2000-(2KTL-6KTL)-L1 User Manual Issue 20 (names DDSU666-H as supported smart power sensor)', 'doc_type': 'manual', 'publisher': 'Huawei (hosted by authorized distributor SKE Solar)', 'revision': 'Issue 20', 'doc_date': '2024-05-30', 'language': 'en', 'region': 'EU', 'accessed': '2026-09-01', 'confidence': 'manufacturer-documented'}] |
| supply_input_voltage_v | 176 V AC - 288 V AC |
| supported_inverter_brands_models | ['Huawei SUN2000-(2KTL-6KTL)-L1 (single-phase power meter recommended for single-phase-only networking; only permitted sensor for the Spanish version)'] |
| voltage_range | 176 Vac ~ 288 Vac (input power and phase voltage) |
Physical / mechanical
| cable_gland_sizes | UNKNOWN |
| depth_mm |
65.5
Huawei Smart Power Sensor datasheet (DDSU666-H / DTSU666-H), Version No.: 02-(20181229) — DDSU666-H column, 'Dimension (H*W*D) 36 * 100 * 65.5mm'
|
| dimensions_h_w_d_mm | 100 mm x 36 mm x 65.5 mm (3.9 in. x 1.4 in. x 2.6 in.) |
| din_modules | UNKNOWN |
| din_rail_type | DIN35 Rail |
| enclosure_material | UNKNOWN |
| height_mm | 100 (INFERRED, same reasoning) |
| mounting_type | ['DIN-rail'] disputed |
| shipping_weight_kg | UNKNOWN |
| torque_specs | UNKNOWN |
| weight_basis | including cables |
| weight_kg |
1.2
Huawei Smart Power Sensor datasheet (DDSU666-H / DTSU666-H), Version No.: 02-(20181229) — DDSU666-H column, 'Weight 1.2 kg (2.6 lb)'
|
| width_mm | 36 (INFERRED ordering: the datasheet label reads 'Dimension (H*W*D) 36 * 100 * 65.5mm'; the current official page for the sibling DTSU666-H gives 'Dimensions (H x W x D) 100 mm x 72 mm x 65.5 mm', i.e. height 100 mm, so 36 mm is the DIN-rail width - consistent with a 2-module single-phase DIN meter) |
Installation
| accessories_supplied | RS485 Cable (10 m / 33 ft.), 1 CT 100 A / 40 mA (5 m / 16.4 ft.) |
| connected_device | Huawei inverter or SmartLogger via RS485 |
| import_export_measurement | UNKNOWN - no explicit sign convention published in the fetched documents. |
| indoor_outdoor | UNKNOWN |
| mounting_orientation | DIN35 rail mount (orientation not stated in the fetched source) |
| topology | DIN-rail mounted at the single-phase grid connection point, one CT on the live conductor. |
Environment
| cooling_method | natural convection (passive) |
| ip_rating | UNKNOWN (not stated in the Smart Power Sensor datasheet) |
| max_altitude_m | UNKNOWN |
| max_operating_altitude_m | UNKNOWN |
| operating_humidity_pct_rh | 5% RH - 95% RH (non-condensing) |
| operating_temperature_c | -25 to +60 |
| relative_humidity | 5% ~ 95% (non-condensing) |
| storage_temperature_c | -40 to +70 |
Interfaces & connectors
| baud_rate_bps | 9600 |
| communication_interface | RS485 |
| ethernet | UNKNOWN |
| modbus_address_range | UNKNOWN for this model (11-19 is documented for DTSU666-H; NOT carried across) |
| modbus_rtu |
Yes (datasheet row 'Protocol Modbus-RTU')
Huawei Smart Power Sensor datasheet (DDSU666-H / DTSU666-H), Version No.: 02-(20181229) — DDSU666-H column, 'Interface RS485' / 'Protocol Modbus-RTU'
|
| modbus_tcp | UNKNOWN |
| protocol | Modbus-RTU |
| protocol_notes | Interface RS485, protocol Modbus-RTU (Smart Power Sensor datasheet 02-(20181229)). Baud rate not stated for this model in the fetched source. |
| register_map_public | UNKNOWN |
| rs485 | Yes |
| wifi | UNKNOWN |
Controls & display
| buttons | UNKNOWN |
| display_type | UNKNOWN |
| leds | UNKNOWN |
Certifications
| emc | ['UNKNOWN'] |
| list | UNKNOWN |
| other | [] |
| regional | ['UNKNOWN'] |
| safety | ['UNKNOWN'] |
Warranty & service
| standard_warranty_years | UNKNOWN |
| standard_years | UNKNOWN |
Documents
datasheet
DTSU666-H 100A - official Specs page (HTML) - used only as the source of the CHINT manufacturer statement for the sibling model
rev UNKNOWN
datasheet
Huawei Smart Power Sensor datasheet (DDSU666-H / DTSU666-H), Version No.: 02-(20181229)
rev 02-(20181229)
datasheet
Smart Power Sensor Technical Specification (DDSU666-H / DTSU666-H / DTSU666-H 250A)
rev 06.2025
Recorded conflicts
physical.mounting_type Review required
['DIN-rail'] — stored value
DIN35 Rail — incoming package
Detected during import huawei-fusionsolar-full-portfolio-2026-09-03
electrical.power_consumption_w Review required
<= 0.8 — stored value
≤ 0.8 W — incoming package
Detected during import huawei-fusionsolar-full-portfolio-2026-09-03
Additional documented parameters
Recorded verbatim from the source; no schema field exists for these yet.
| Input Power | 176 Vac ~ 288 Vac |
| Mounting Type | DIN35 Rail |
| Power Grid Type | 1P2W |
| identity.region_as_researched | GLOBAL |
| identity.variant_as_researched | single-phase, 100 A via one CT |
| manufacturer_legal_entity_as_printed | HUAWEI |