ANMASystem BuildingAutomation, Network, Monitoring & Analytics
PREMIUM

Knowledge BaseSmart Meters

Huawei DTSU666-H 250A/50mA

Official manufacturer GLOBAL verified Sept. 3, 2026

Identity

category smart_meters
legal_entity_on_user_manual HUAWEI DIGITAL POWER TECHNOLOGIES CO., LTD.
manufacturer Huawei
marketing_name Smart Power Sensor
model DTSU666-H 250A/50mA
note Distinct product from the 100 A DTSU666-H: different CT set, different CT ratio (5000:1 vs 2500:1) and a wider measurement range. Not merged.
region GLOBAL
variant 250 A / 50 mA (supplied with 250 A / 50 mA CTs)

Electrical

accuracy_class Class 1 (user manual)
accuracy_current_voltage_pct ± 0.5%
accuracy_power_energy_pct ± 1%
ct_ratio 250 A / 50 mA (5000:1)
ct_secondary_output_ma 50
ct_supplied three 250 A / 50 mA CTs
frequency_hz 50 / 60
measurement_current_a 0 - 250 A
measurement_line_voltage_v 304 V AC - 499 V AC
measurement_method external current transformers (not direct)
measurement_phase_voltage_v 176 V AC - 288 V AC
nominal_voltage_v 230 V AC / 400 V AC
phase_configuration three-phase
power_consumption_w ≤ 1 W
power_grid_type 3P4W or 3P3W

Physical / mechanical

dimensions_h_w_d_mm 72 x 100 x 65.5 mm
din_modules 4
mounting_type DIN35 Rail
weight_basis including cables (datasheet)
weight_kg 1.5

Installation

connected_device Huawei inverter or SmartLogger via RS485
import_export_measurement Measured at the grid-connection point; CT orientation must follow the arrow direction shown in the wiring diagram. No explicit sign convention for import vs export is published in the fetched documents.
topology DIN-rail mounted at the grid connection point. Three-phase four-wire: Ua, Ub, Uc, Un to terminals 3, 6, 9, 10. Three-phase three-wire: Ua, Uc, Ub to terminals 3, 9, 10. CT outputs IA*, IA, IB*, IB, IC*, IC to terminals 13, 14, 16, 17, 19, 21.

Environment

ip_rating UNKNOWN
max_operating_altitude_m UNKNOWN
operating_humidity_pct_rh 5% RH - 95% RH (non-condensing) per datasheet; ≤75% RH per user manual
operating_temperature_c -25 to +60
storage_temperature_c -40 to +70

Interfaces & connectors

baud_rate_bps 9600 (datasheet); 4800 / 9600 selectable per quick guide
communication_interface RS485
modbus_address_range 11-19
protocol Modbus-RTU
register_map_public UNKNOWN

Certifications

list UNKNOWN

Warranty & service

standard_warranty_years UNKNOWN

Documents

datasheet Smart Power Sensor Technical Specification (DDSU666-H / DTSU666-H / DTSU666-H 250A) rev 06.2025
quick_guide DTSU666-H and DTSU666-H 250 A/50mA Smart Power Sensor Quick Guide rev Issue 03
user_manual DTSU666-H 100 A and 250 A Smart Power Sensor User Manual (Huawei official, distributor-hosted mirror) rev Issue 06

Recorded conflicts

environment.operating_humidity_pct_rh Review required
5% RH - 95% RH (non-condensing) — Huawei Smart Power Sensor datasheet 06.2025
≤75% RH — DTSU666-H User Manual Issue 06
physical.weight_kg Review required
1.5 kg — Huawei Smart Power Sensor datasheet 06.2025
≤ 0.8 kg — DTSU666-H User Manual Issue 06 (2024-05-06)

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

manufacturer_legal_entity_as_printedCHINT

Build a system with this product